12 Parameter list / legend of parameter bit fields LMU...
07.11.2002
No
Name
Group
Function
Range
No
QAA73
AGU2.310
Level
QAA73
AGU2.310
LevelNo
PC_Tool
Level
PC_Tool
526 KonfigEingangR
AGU2.51x
Progr input on clip-in function module
0 ... 255
618
Engineer
5
Installer
471 KonfigAusgang
Boiler
Function programmable output K2 LMU
0 ... 255
615
Engineer
5
Installer
523 KonfigAusgang1R
AGU2.51x
Function output1 clip-in function module
0 ... 255
619
Engineer
5
Installer
524 KonfigAusgang2R
AGU2.51x
Function output2 clip-in function module
0 ... 255
620
Engineer
5
Installer
525 KonfigAusgang3R
AGU2.51x
Function output3 clip-in function module
0 ... 255
621
Engineer
5
Installer
529 PAnfoExtSchwelle
AGU2.51x
Threshold of analog signal from which the external
demand for output will be accepted (percentage of
maximum value of analog signal)
5 ... 95 %
623
Engineer
5
Installer
All non-safety-related time parameters
130 ZqNach
Heating mode
Overrun time of pumps, max. 210 min (setting 255:
continuous operation of Q1)
0 ... 255 min
544
Engineer
5
Installer
134 ZkickFkt
Boiler
Time for kick function of pump / diverting valve outputs
0 ... 51 s
584
Engineer
5
Installer
139 ZBreMinP
Boiler
Minimum burner pause time (heat demand-dependent
switching hysteresis)
0 ... 3600 s
545
Engineer
5
Installer
140 ZBreMinL
No meaning
Minimum burner running time (heat demand-dependent
switching hysteresis)
0 ... 255 s
546
Engineer
5
Installer
141 ZReglVerz
Boiler
Controller delay after burner is started up
0 ... 255 s
547
Engineer
5
Installer
136 ZAueRuec
Boiler flue gas supervision Reset time of flue gas supervision equipment
10 ... 218 min
3
OEM
(production)
329 ZsdHzEnde
Boiler
Time until switch-off differential is reduced to
SdHzAusMin
0 ... 210 min
588
OEM
4
OEM service
330 ZsdBwEnde
DHW
Time until switch-off differential is reduced to
SdBwAusMin
0 ... 210 min
589
OEM
4
OEM service
331 ZSperrDynAusSd
Boiler
Locking time of dynamic switch-off differential after a
change of heating<->DHW
0 ... 51 s
590
OEM
4
OEM service
430 Z_BwComfort1
DHW-inst DHW heater
Time for instantaneous DHW heater Comfort function
after consumption (when there is no demand for heat)
(0 = deactivated; 1440 = continuously)
0 ... 1440 min
602
Engineer
5
Installer
460 Z_BwComfort2
DHW-inst DHW heater
Time for instantaneous DHW Comfort function after
consumption (when there is demand for heat) (0 =
deactivated; 255 = 4h15min)
0 ... 255 min
603
Engineer
5
Installer
475 ZqComfortAus
DHW-DLH
Time for pump overrun in Dlh Comfort function with
burner off (0 = pump off with burner off; 255 = pump
always on)
0 ... 255 min
5
Installer
Setting the controller's dynamics
158 KpBw
DHW
Proportional coefficient of DHW controller
0 ... 15.9375
566
OEM
4
OEM service
159 TvBw
DHW
Derivative action time of DHW controller
0 ... 15.9375 s
567
OEM
4
OEM service
160 TnBw
DHW
Integral action time of DHW controller
0 ... 4000 s
568
OEM
4
OEM service
161 KpHz1
Heating mode HC1
Proportional coefficient of heating circuit controller
0 ... 15.9375
569
OEM
4
OEM service
162 TvHz1
Heating mode HC1
Derivative action time of heating circuit controller
0 ... 15.9375 s
570
OEM
4
OEM service
163 TnHz1
Heating mode HC1
Integral action time of heating circuit 1 controller
0 ... 4000 s
571
OEM
4
OEM service
167 KpDt
PWM pump
Proportional coefficient of dT control
0 ... 15.9375
575
OEM
4
OEM service
168 TvDt
PWM pump
Derivative action time of dT control
0 ... 15.9375 s
576
OEM
4
OEM service
169 TnDt
PWM pump
Integral action time of dT control
0 ... 4000 s
577
OEM
4
OEM service
170 ZAbtastK
Boiler
Sampling time of temperature control loop in heating
mode and with storage tank charging
1 ... 4 s
578
OEM
4
OEM service
171 ZAbtastDlh
DHW-inst DHW heater
Sampling time of temperature control loop with
instantaneous DHW heater
1 ... 4 s
579
OEM
4
OEM service
Setpoints, actual values and limit values
436 pH2OAbschalt
Boiler water pressure
supervision
Water pressure above which boiler and pump will be
shut down
0 ... 25.5 bar
594
Engineer
5
Installer
156 pH2Omin
Boiler water pressure
supervision
Minimum boiler water pressure
0 ... 25.5 bar
562
Engineer
5
Installer
157 pH2Omax
Boiler water pressure
supervision
Maximum boiler water pressure
0 ... 25.5 bar
563
Engineer
5
Installer
437 SdpH2O
Boiler water pressure
supervision
Switching differential of water pressure
0 ... 25.5 bar
595
Engineer
5
Installer
177 FoerderMin
PWM pump
Min head of modulating pump (supplier specification)
0 ... 25.5 m
565
OEM
4
OEM service
176 FoerderMax
PWM pump
Max head of modulating pump (supplier specification)
0.5 ... 25.5 m
564
OEM
4
OEM service
479 dpH2OminPuOn
Boiler water pressure
supervision
Min pressure differential to be reached after the pump
was switched on
0 ... 5 bar
616
Engineer
5
Installer
480 dpH2OmaxPuOn
Boiler water pressure
supervision
Max pressure differential that can occur when pump is
switched on
0 ... 5 bar
617
Engineer
5
Installer
Controller functions (cont‘d
Controller times
Controller coefficients
Pressures