Siemens Industry, Inc.
A5E31166555A-001
Wiring Diagram (Electrically Held Contactor)
Refer to control module instruction sheets
for wiring of mechanically held contactors.
Class LC Electrically Held Lighting Contactor
(Convertible to Mechanically Held)
Catalog numbers LCE00C*
Page 5 of 6
Notes:
1. Refer to the NEC or local electric code as required.
2. Additional over current protection for control circuit may be required.
3. When coil and line voltages are same, the control voltage may be derived
from the line for supply.
4. Ground lug kit number 49D11960001 meets CSA standard 22.2 no. 14-1973
and is rated for 1 conductor 2-14 AWG AL/CU wire.
Contacts in positions 1 through 4 can be used as either NO or NC.
Contacts in positions 5 and 6 can be used only as NO.
Main contacts are shown in open position.
Line and load terminals are reversible.