Coil Replacement for Electrically Held Contactors

Step 1: Remove the coil cover.

Class LC Electrically Held Lighting Contactor

(Convertible to Mechanically Held)

Catalog numbers LCE00C*

Page 3 of 6

Step 2: Remove coil assembly.

Step 3: Replace with new coil.

Step 4: Reinstall coil assembly and cover.

Torque 7 - 12 lb-in

Siemens Industry, Inc.    

 

 

 

 

 

 

 

 

 

 

A5E31166555A-001

Summary of Contents for LCE00C Series

Page 1: ...iary contact blocks are available in either single pole 49LCAC1PA or double pole 49LCAC2PA versions Auxiliary contacts can be installed on either side of the base When installed on the RIGHT side the auxiliary contact functions as a N C contact When installed on the LEFT side the auxiliary contact functions as a N O contact 2P 2P 2P 2P 2P 2P 2 P 2 P 2 P 2 P 2 P 2 P Electrically Held Standard Mecha...

Page 2: ...t from the N C indicator side Pull clip position power pole module onto the base and release 1 2 1 2 N F 1 2 N O N C Power Pole Installation Removing the Power Pole Modules Remove power pole module by inserting screwdriver into the plastic clip and pull it out to release the power pole module from the base 1 1 Auxiliary Contact Block Installation Insert one end of auxiliary contact module Snap opp...

Page 3: ... cover Class LC Electrically Held Lighting Contactor Convertible to Mechanically Held Catalog numbers LCE00C Page 3 of 6 Step 2 Remove coil assembly Step 3 Replace with new coil Step 4 Reinstall coil assembly and cover Torque 7 12 lb in Siemens Industry Inc A5E31166555A 001 ...

Page 4: ...e contactor is in the unlatched state If in the latched state push both tabs forward and release The Contactor should return to the unlatched state Class LC Electrically Held Lighting Contactor Convertible to Mechanically Held Catalog numbers LCE00C Page 4 of 6 Step 3 Remove coil assembly Siemens Industry Inc A5E31166555A 001 Unlatched state Latched state Step 4 Replace with new coil Step 5 Replac...

Page 5: ... electric code as required 2 Additional over current protection for control circuit may be required 3 When coil and line voltages are same the control voltage may be derived from the line for supply 4 Ground lug kit number 49D11960001 meets CSA standard 22 2 no 14 1973 and is rated for 1 conductor 2 14 AWG AL CU wire Contacts in positions 1 through 4 can be used as either NO or NC Contacts in posi...

Page 6: ... 2 18 14 60o 75o C CU 15 Auxiliary Contacts 1 or 2 22 12 60o 75o C CU 7 12 8 AWG is stranded only For replacement parts information or an application guide visit our website at usa siemens com controls or contact your local Siemens sales office Siemens Industry Inc 5300 Triangle Parkway Norcross GA 30092 1 800 241 4453 info us siemens com usa siemens com controls Subject to change without prior no...

Reviews: