Torque

10 - 15 lb-in

E87010-A0164-T003-A6-LCN0  

Class LC Electrically Held Lighting Contactor

(Convertible to Mechanically Held)

Catalog numbers LCE00C*

Page 1 of 6

August, 2012

Power Pole Modules

 

Power pole modules are available in either single pole 
(49LCPP1A) or double pole (49LCPP2A) versions.

Main Base

 

The base of the lighting contactor has provisions to 
accept up to six power pole modules for a total of  
twelve power poles. A combination of normally open 
(N.O.) and normally closed (N.C.) contacts may be  
assembled but with a maximum of eight N.C. contacts.

Control Module Kits

Conversion from an electrically held to a mechanically held 
contactor can be accomplished with a control module kit. 
Kits are available for both 2-wire and 3-wire control in a  
variety of control voltages. The control module is available 
up to 277V maximum. For control voltage greater than 
277V, use a control transformer. Refer to Replacement 
Parts and Accessories for catalog numbers. Instruction 
and wiring diagrams can be found in the control module 
instruction sheets.

Assembly

Positions 1 through 4 on the base can be  
configured to either normally open (N.O.) or  
normally closed (N.C.) while positions 5 and 6  
can only be configured as normally open (N.O.).  
Each position can accept one power pole module.  
Each power pole module can consist of either a  
single or double power pole.

Auxiliary Contact

The auxiliary contact blocks are  
available in either single pole  
(49LCAC1PA) or double pole  
(49LCAC2PA) versions. Auxiliary  
contacts can be installed on either  
 side of the base. When installed on  
the RIGHT side, the auxiliary contact 
functions as a N.C. contact. When 
installed on the LEFT side, the auxiliary 
contact functions as a N.O. contact.

2P

2P

2P

2P

2P

2P

2P

2P

2P

2P

2P

2P

Electrically Held (Standard)

Mechanically Held (Optional)

2P

2P

2P

2P

2P

2P

2P

2P

2P

2P

2P

2P

Position 1

Pos. 2

Pos. 3

Pos. 4

Pos. 5

Pos. 6

IMPORTANT

THESE  INSTRUCTIONS  DO  NOT  PURPORT  TO  COVER  ALL  DETAILS  OR  VARIATIONS  IN  EQUIPMENT,  NOR 
TO  PROVIDE  FOR  EVERY  POSSIBLE  CONTINGENCY  TO  BE  MET  IN  CONNECTION  WITH  INSTALLATION  
OPERATION  OR  MAINTENANCE.  SHOULD  FURTHER  INFORMATION  BE  DESIRED  OR  SHOULD  PARTICULAR 
PROBLEMS  ARISE  WHICH  ARE  NOT  COVERED  SUFFICIENTLY  FOR  THE  PURCHASER’S  PURPOSES,  THE  
MATTER SHOULD BE DEFERRED TO THE LOCAL SIEMENS SALES OFFICE. THE CONTENTS OF THIS INSTRUCTION 
MANUAL  SHALL  NOT  BECOME  PART  OF  OR  MODIFY  ANY  PRIOR  OR  EXISTING  AGREEMENT,  COMMITMENT 
OR RELATIONSHIP. THE SALES CONTRACT CONTAINS THE ENTIRE OBLIGATION OF SIEMENS. THE WARRANTY 
CONTAINED IN THE CONTRACT BETWEEN PARTIES IS THE SOLE WARRANTY OF SIEMENS. ANY STATEMENTS 
CONTAINED HEREIN DO NOT CREATE NEW WARRANTIES OR MODIFY THE EXISTING WARRANTY.

Mounting

Contactor must be mounted in the vertical  
position on a sturdy support.

WARNING

Hazardous voltage
Can cause death or serious injury.

Disconnect main power and control voltages before
installation or maintenance on the equipment.

usa.siemens.com/controls

Instruction sheet

Summary of Contents for LCE00C Series

Page 1: ...iary contact blocks are available in either single pole 49LCAC1PA or double pole 49LCAC2PA versions Auxiliary contacts can be installed on either side of the base When installed on the RIGHT side the auxiliary contact functions as a N C contact When installed on the LEFT side the auxiliary contact functions as a N O contact 2P 2P 2P 2P 2P 2P 2 P 2 P 2 P 2 P 2 P 2 P Electrically Held Standard Mecha...

Page 2: ...t from the N C indicator side Pull clip position power pole module onto the base and release 1 2 1 2 N F 1 2 N O N C Power Pole Installation Removing the Power Pole Modules Remove power pole module by inserting screwdriver into the plastic clip and pull it out to release the power pole module from the base 1 1 Auxiliary Contact Block Installation Insert one end of auxiliary contact module Snap opp...

Page 3: ... cover Class LC Electrically Held Lighting Contactor Convertible to Mechanically Held Catalog numbers LCE00C Page 3 of 6 Step 2 Remove coil assembly Step 3 Replace with new coil Step 4 Reinstall coil assembly and cover Torque 7 12 lb in Siemens Industry Inc A5E31166555A 001 ...

Page 4: ...e contactor is in the unlatched state If in the latched state push both tabs forward and release The Contactor should return to the unlatched state Class LC Electrically Held Lighting Contactor Convertible to Mechanically Held Catalog numbers LCE00C Page 4 of 6 Step 3 Remove coil assembly Siemens Industry Inc A5E31166555A 001 Unlatched state Latched state Step 4 Replace with new coil Step 5 Replac...

Page 5: ... electric code as required 2 Additional over current protection for control circuit may be required 3 When coil and line voltages are same the control voltage may be derived from the line for supply 4 Ground lug kit number 49D11960001 meets CSA standard 22 2 no 14 1973 and is rated for 1 conductor 2 14 AWG AL CU wire Contacts in positions 1 through 4 can be used as either NO or NC Contacts in posi...

Page 6: ... 2 18 14 60o 75o C CU 15 Auxiliary Contacts 1 or 2 22 12 60o 75o C CU 7 12 8 AWG is stranded only For replacement parts information or an application guide visit our website at usa siemens com controls or contact your local Siemens sales office Siemens Industry Inc 5300 Triangle Parkway Norcross GA 30092 1 800 241 4453 info us siemens com usa siemens com controls Subject to change without prior no...