Operation
5
Switching off / Switching on
119
Building Technologies
A6V10380629_en--_a
Fire Safety
2015-09-10
a
The 'Select command' dialog window opens.
8. Select the 'RT FIRE channels OFF' command.
a
The command execution display confirms successful execution of the
command by displaying
.
a
The 'RT Fire' is switched off.
a
The LED 'Remote alarm Off' on the Person Machine Interface is illuminated.
Switching on the 'RT Fire'
l
Proceed as with switching off, but select the 'ON' command.
5.3.5 Switching off alarm activation
WARNING
System parts that have been switched off make it impossible to acquire and
process alarms or faults!
Fire may spread unhindered.
● Deploy staff to monitor the deactivated area.
● You must switch deactivated parts of the ↑ 'Site' back on as soon as possible.
WARNING! System parts that have been switched off make it impossible to
acquire and process alarms or faults! You can ↑ switch off the fire detection
installation alarm activation for specific elements with this function.
Faults such as the removal of a detector are nevertheless evaluated and displayed.
You can only run the 'Alarm evaluation OFF' command on the following elements:
'XC10 zone'
↑ 'Section'
'Automatic zone'
'Technical zone'
Alarm evaluation OFF
w
You are logged onto at least 'Access level' 2.1.
1. Press the button 'Topology' on the GTB.
a
The 'Topology' dialog window opens.
2. Press 'Lower level' in the 'Detection tree' list entry.