Operation
5
ALARM procedure
103
Building Technologies
A6V10380629_en--_a
Fire Safety
2015-09-10
Step
Action / Condition
Consequence / Status
1
Press the 'Acknowledge' button
or
press <Acknowledge> on the Person
Machine Interface
⇨ With 'AVC' countdown t2 for examination of the
cause of 'ALARM' starts
2
Reading the status information:
l
'Fire Brigade requested'
⇨ 'ALARM' is transmitted to fire brigade
l
'Fire Brigade in' 'mm:ss'
⇨ 'ALARM' is transmitted to fire brigade in mm:ss
⇨ Remaining time is shown as Countdown
l
'Call Fire Brigade !' if:
– Remote transmission switched off
– Remote transmission blocked or
defective
– No remote transmission available
⇨ Fire brigade must be called by phone!
⇨ No automatic transmission to fire brigade
3
Press the 'Intervent.txt.' button if displayed
⇨ Intervention text is displayed
4
Read off fire location on display
5
Optional: press <Alarm device> on the
Person Machine Interface (password
required)
⇨ Deactivates the acoustic alarm devices
6
Go to the fire location
7
Decide: MAJOR INCIDENT or minor incident
Condition
MAJOR INCIDENT
Minor incident
Fire brigade has been called
Save people
Guide the fire brigade to the fire
location
Fight the fire
Try to prevent fire brigade
deployment
'Fire Brigade in' 'mm:ss'
Countdown is running
Trigger the manual call point
immediately
or
Press 'All alarm delays off'
Press 'Reset' (password required)
'Call Fire Brigade !'
No automatic transmission to
the fire brigade
Call the fire brigade on the phone!
Press 'Reset' (password required)
A password is required for resetting.
It may be necessary to air the room before 'Reset' is possible.
You can temporarily switch off elements that cannot be reset.