Mounting
Laying the cables and connecting the batteries
4
18 | 32
Building Technologies
A6V10393194_d_en_--
Fire Safety
2018-11-05
The following instructions must be observed.
●
The cable cross section for each of the three lines of the mains cable is
1.5…2.5 mm
2
.
●
The mains cable must be inserted from above on the left of the housing and
must not be laid outside the boundary of the mains zone.
●
The lines of the mains cable must be secured with a cable tie.
●
Signal lines must only be fed into the housing on the right from above or from
the rear.
●
Signal lines must be secured with a cable tie.
●
Cable entries must be closed completely.
●
No cable entries should be made in the back box.
●
Batteries must be installed so that they cannot leak.