FS-100 Installation & Operation Manual
P/N 315-699461
41
Total Standby Current
(from above)
Hours of Standby Required per
NFPA 72 Standard (4, 24 or 60)
AH for Standby
A.
x ____ Hours
=
Total Alarm Current
(from above)
5 Minutes of Alarm Operation
per NFPA 72 Standard*
AH for Alarm
A.
x 0.33 Hours
=
A.H. for
Standby
A.H. for
Alarm
Calculated
A.H.
De-rating
Factor
A.H. Required
Battery Capacity
+
=
X 1.25
=
Notes:
1.
An additional multiplier is included to compensate for the higher discharge rate in alarm. Battery capacity decreases with age.
2.
The Standby c Alarm current must never exceed 3.0 Amps
3.
The following states the maximum standby current allowed using a 38 AH battery set:
60 hours of standby time is 0.5 Amps
24 hours of standby time is 1.2 Amps
4.
Does not include lamp or LED current, add separately.
5.
When using the FS-MT Municipal Tie Module add the following currents for standby and alarm:
Type of Municipal Tie Connection
Standby
Alarm
Local Energy
+ 0
+ 0
Reverse Polarity Alarm Output (CA)
Alarm
Alarm w/Trouble
+ 0.020
+ 0
+ 0.020
+ 0.020
Reverse Polarity Trouble Output (CT)
+ 0.020
+ 0.020