6
Operation
The 'device' function
46
Building Technologies
008250_i_en_--
Fire Safety
2013-08-15
Assignment of outputs
The assignment of the outputs A, B, C, D depends on the line device.
Line device
Output A
Output B
Output C
Output D
Notes
Point detector (thermal
/ optical)
Ext. AI
Activation of
evacuation signal
Activation of alarm
signal
-
-
Manual call point
Ext. AI
-
-
-
Not available for all line
devices
Linear smoke detector Ext. AI
-
-
-
-
Flame detector
Ext. AI
-
-
-
-
Input/
output modules
Activation
of relay
Activation of relay
Activation of relay Activation of
relay
If output available
Transponder
Activation
of relay
Activation of relay
Activation of relay Activation of
relay
If configured as output
Aspirating smoke
detector
Reset
Day / Night
Standby
Normalize
-
Video fire controller
Start
receptacle
Start receptacle
-
-
-
Alarm sounder
Ext. AI
Activation of
evacuation signal
Activation of alarm
signal
-
-
Alarm sounder with
additional optical
indicator
Ext. AI
Activation of
evacuation signal
Activation of alarm
signal
Activating the
beacon
-
Sounder interbase
Ext. AI
Activation of
evacuation signal
Activation of alarm
signal
-
-
Sounder interbase with
additional optical
indicator
Ext. AI
Activation of
evacuation signal
Activation of alarm
signal
Activating the
beacon
-
Addressable alarm
indicator
Ext. AI
-
-
-
-
Radio gateway
Ext. AI
-
-
-
-