Operation
6
The 'device' function
45
Building Technologies
008250_i_en_--
Fire Safety
2013-08-15
6.2
The 'device' function
The 'Devices' function is not available in 'EL' operation mode.
Meaning of the lines
The display shows the function of the line device in four lines. The internal and
external alarm indicator of the selected line device flash.
Line
Display
1
Input status
Input fault
Line device fault
Outputs A, B, C, D
Disconnector status
Output of external alarm indicator
2
Address for line device
Status of first line
3
Name of the line device
Cursor (position display) for editing
4
The serial number (identification number) and product version (ES) of the line device
The position display when editing in plain text
If a line device has already been operated on a control panel, it will not be
initialized again. The existing configuration is adopted by the control panel.
Example:
In the case of the FC20xx, FC72x or AlgoRex fire control panels, the inputs of a
FDCIO222 that are not used (= not linked) are directly set to 'off' in the line device.
The input status of the FDUL221 line tester is therefore not displayed.
Meaning of inputs
The display depends on the line device connected. The following table shows how
the FDUL221 line tester displays inputs:
Danger level Meaning
Display
Input status
Display
Input status
Display
0
No danger
'0'
Free
'-'
Not active
'-'
1
Possible danger
'1'
Resetting /
Not ready
'r'
2
Probable danger
'2'
Initial activation /
testing
'a'
Active
'a'
3
Most likely danger
'A'
Alarm activation
'A'