Setup and function
17
Building Technologies
007025_i_en_--
Fire Safety & Security Products
07.05.2010
3.2.4
Diagnosis levels
The FDSB291 sounder base monitors its operation largely autonomously.
The following diagnosis levels are derived from the different control measurements:
Normal
Observe information
Fault
For details, see table below.
When a fatal error occurs, which impairs the proper function of the sounder base, a
fault message is signaled. To remedy the cause, additional information is available
in the sounder base. This can be displayed by the detector exchanger and tester
FDUD292 or the intelligent detector tester FDUD293, for example.
For details, see Documents 007227 and 009718.
Information displayed on the
detector exchanger and
tester
Meaning
Measures
'no deviation'
Normal, no fault is present
The sounder base is fully functional
None
'maybe excha.'
1
Observe information
Sounder base present, but parameters not
set
Set permissible parameters
Fault present
Invalid parameter settings (e.g. no sounder
base present)
Set valid parameters
Connect sounder base
Sounder base defective (Piezo monitoring) Replace sounder base
Any fault message
Short-circuit on sounder base connection
Remedy short-circuit
The status 'Any fault message' can be displayed together with another status,
e.g. 'needed excha.' (replacement necessary).
1
The information displayed on the detector exchanger and tester is always in
English; no translation into the corresponding language.