
Specifications
Technical data FDSB221
8
31
Building Technologies
A6V10320090_c_en_--
Fire Safety
02.11.2011
8
Specifications
8.1
Technical data FDSB221
Detector line
Operating voltage
DC 12…33 V
Operating current:
Standby
250 μA
Sound activated
3,5 mA
Quiescent current connection factor
1
Address connection factor
1
Separator connector factor
1
Protocol
FDnet
System compatibility
See 'List of compatibility'
Connection factor: Sound activated
15
Line separator
Line voltage:
Nominal
DC 32 V (= V
nom
)
Minimum
DC 12 V (= V
min
)
Maximum
DC 33 V (= V
max
)
Voltage at which the separator opens:
Minimum
DC 7.5 V (= V
SO min
)
Maximum
DC 10.5 V (= V
SO max
)
Permanent current when switches are closed:
Max. 0.5 A (= I
C max
)
Switching current (e.g. in the event of a short-circuit)
Max. 1 A (= I
S max
)
Leakage current when switches are open:
Max. 1 mA (= I
L max
)
Serial impedance when switches are closed:
Point detector not used
0.5 Ω (= Z
C max
)
Point detector used
2x 0.5 Ω
Function
Number of selectable tones
11
Number of programmable activation levels
2
Number of programmable sound levels
1 alarm sound level according to EN 54-3
2 test sound levels
3
Adjustable maximum sound levels (typical values in
dBA/m at DC 32 V with cover plate FDBZ296)
For details, see 'Annex technical data'
77…83 dBA