Planning
4
Configuration
24
Building Technologies
A6V10320090_c_en_--
Fire Safety
02.11.2011
4.5.2
Optical signals
No.
Flash type
Flashing
frequency
Pulse pattern
Luminous intensity at 32 V,
angle-dependent (typ.)
Standard / Notes
0
Flash
0.8 Hz
20 ms
1.25 s
Normal
1
Flash
0.8 Hz
20 ms
1.25 s
Normal
Supervision function
1
2
Alternating
2
0.8 Hz
10 ms 10 ms
1.25 s
Normal
3
Flash
0.8 Hz
5 ms
1.25 s
Dark
4
Flash
0.8 Hz
35 ms
1.25 s
Bright
5
Flash
0.8 Hz
35 ms
1.25 s
Bright
Supervision function
1
6
Alternating
2
0.8 Hz
17.5 ms
17.5 ms
1.25 s
Bright
7
Reserve
-
-
-
-
1
Supervision function: Each LED is activated once every 24 hours and flashes 4
times in succession.
2
In alternating mode, only half of the LEDs flash. After a pause of 50 ms the
other half flash.
See also
Beam characteristics of the LEDs on the sounder beacon
interbase (DC 32 V) [➙ 39]