Installation
Intended use
The manual call point FDM243H triggers an alarm when the
glass insert is pushed in and the alarm button is pressed
(indirect activation). The alarm is immediately transmitted to
the control panel.
When the alarm is activated, the switching unit must be reset
and a new glass insert installed.
Preparation
1.
Push the keyhole cover (2) to the right.
2.
Open the door with the key supplied (1).
3.
Pull out the key and keep it in a safe place.
4.
Close the keyhole cover.
5.
Unscrew the four Allen head screws (4) and remove the
switching unit (5).
6.
Determine how the cable should be entered in the housing
from below.
7.
Remove the cable gland (7), which is not required, and
replace it with a V-pin M20 x 1.5 (6).
Do not unscrew the four cross-head screws on the
switching unit.
Do not remove or damage the screw connection on
the rear wall of the housing.FD
Installation
CAUTION!
Electrical voltage on lines
Risk of injury due to electric shock
During installation work, electrical voltage must not
be applied to the lines
Observe the country-specific regulations for the
exact installation height!
1.
Secure the housing at a height of 0.9…1.6 m on an even
surface.
2.
Only use the two screw holes marked with arrows in the
figure.
3.
Secure the housing using two screws (3).
4.
Pull the cables through the entry opening(s) into the
housing.
5.
Tighten the cable gland so that it is properly sealed.
Connecting the switching unit to the electricity
1.
Connect the feed line to the spring clips on the rear side of
the switching unit, in accordance with the connection
diagram.
2.
If the detector line cables (LINE) are shielded, connect the
shielding (SHIELD).
3.
Connect the shielding of the external alarm indicator cable
with the positive pole of the external alarm indicator
connection.
Note the positive and negative poles.
Only connect one wire per terminal. This is the only
way to ensure the connection is failure-free for the
entire service life of the device.
The shielding must not touch any other potentials or
metal parts in the manual call point.
4.
When inserting the switching unit into the housing, note the
feed line. Avoid crushing the feed line.
5.
Secure the switching unit in the housing using the four
Allen head screws (4).
WARNING!
Deactivating the manual call points prevents
alarms from being forwarded
Alarming does not take place
Mark deactivated or non-functional manual call
points with "NOT IN USE"!
6.
Close the door.
You will find more information in
document A6V10374021.