4

Siemens Industry, Inc.
Building Technologies Division

A6V10324662_g_en_US

 

201

6

-0

1

-

20

MOUNTING

Input/output module FDCIO422 can be mounted
directly into a 4

11

/

16

-inch square box or 5-inch

square box.
An additional extension ring can be mounted on
the 4

11

/

16

-inch square box with two screws.

For mounting the input/output module in the
5-inch square box use a 4

11

/

16

-inch adapter

plate.

Fasten the module to the square box with the
4 screws provided with the box.
Fasten the faceplate on the carrier using the
2 screws provided with the FDCIO422.

Be sure to program the FDCIO422 before
fastening the faceplate to the unit.

Volume allowance FDCIO422

FDCIO422 Volume 11.7 inch

3

,

max. 20 conductors
Check NFPA70, National Electric Code
‘314.16 Number of Conductors in Outlet,
Device and Junction Boxes, and Conduit’,
Table 314.16(A) and (B), to choose the
correct metal box (4

11

/

16

-inch square box,

4

11

/

16

-inch square box with extension ring

or 5-inch square box).

WARNING

It is not allowed to use the module without
the faceplate. Remove the faceplate for
service and maintenance reasons only!

Figure 7 Mounting the FDCIO422

TECHNICAL DATA

Operating voltage:

DC 12 – 32 V

Operating current
(quiescent):

1 mA

Absolute maximum
peak current:

1.92 mA

Maximum current
connection factor

2)

:

4

Relays output

1)

:

(normally open /
normally closed)

DC 30 V / AC 125 V
Max. 4x 5 A or
2x 7 A (OUT B, C) or
1x 8 A (OUT C)

Operating
temperature:

32 – 120 °F / 0 – 49 °C

Storage temperature:  -22 – +140 °F / -30 – +60 °C
Humidity:

5 – 85 % R.H. (not freezing
and condensing at low
temperature)

Communication
protocol:

FDnet (supervised Signaling
line circuit, Power limited)

Color:

Carrier: ~RAL 9017
Cage cover: transparent
Cage: ~RAL 9017
Faceplate: white

Standards:

UL 864, ULC-S 527, FM 3010,

 

UL 2572

Approvals:

UL / ULC / FM

System compatibility  FC2005, FC2025, FC2050,

FV2025, FV2050, FC901,
FC922, FC924, FV922,
FV924 & FireFinder XLS

Dimensions:

4.1 x 4.7 x 1.2 inch

Volume (cage and
carrier):

11.7 inch

3

1)

2 coil latching type, dry contact, Form A

2)

Average charge current of the device. 1 Load Unit (LU)
equals to 250 µA

11

16

1

8

11

16

ADAPTER PLATE

11

16

4     INCH EXTENSION RING

INCHES DEEP (29.5 in³)

FDCIO422

CONTROL MODULE BARRIER

(SUPPLIED)

FACEPLATE
5

INCHES

(SUPPLIED)

½

Summary of Contents for FDCIO422

Page 1: ...ing type form A relay contacts for fire control installations Status indication per LED for each input and output plus 1 LED for general status of the device Power supply via FDnet supervised power limited Including 4 EOL devices 470 Ω 3 separators to separate the power limited wiring from the non power limited Separators are delivered in 3 different sizes for standard 4 11 16 inch box 4 11 16 inc...

Page 2: ...se follow the corresponding description of the Panel used WIRING Refer to Figure 11 Refer to the appropriate wiring diagram and wire the addressable input output module accordingly Recommended wire size 18 AWG minimum and 14 AWG maximum Wire larger than 14 AWG can damage the connector Refer to Figures 2 and 3 Follow the instructions in the DPU manual or 8720 manual to program the FDCIO422 to the d...

Page 3: ...n power limited fire protection signaling conductors For the FDCIO422 wiring to the terminal block for line and inputs must enter the outlet box separately from the terminals for outputs For the output terminals protection with a fuse is recommended Refer to Figures 6 and 9 WIRING AT THE TERMINAL BLOCKS Minimize the length of wire entering the outlet box Figure 6 Power Limited Wiring Separators Th...

Page 4: ...se the module without the faceplate Remove the faceplate for service and maintenance reasons only Figure 7 Mounting the FDCIO422 TECHNICAL DATA Operating voltage DC 12 32 V Operating current quiescent 1 mA Absolute maximum peak current 1 92 mA Maximum current connection factor 2 4 Relays output 1 normally open normally closed DC 30 V AC 125 V Max 4x 5 A or 2x 7 A OUT B C or 1x 8 A OUT C Operating ...

Page 5: ...ptable means Insulate shields do not make any connections to the device or back box 16 Use shielded and or twisted wire to connect the switch wiring and keep the wiring as short as possible 17 Tie the switch wiring shield to the local earth ground at only one end refer to Figure 9 For multiple switches on the same input connect incoming and outgoing shields together in an acceptable means Insulate...

Page 6: ...l Remedy cause Note Any general message can be displayed together with another status Configuring the outputs Configuring the inputs For configuring the outputs proceed as follows a Determine in which position the contact is active The contact can be active when it is Closed normally open NO Open normally closed NC b After activating the contact remains Permanently active Active only for a certain...

Page 7: ...10 FDCIO422 input wiring Class A and Class B for details of Line 1 and 2 wiring see Figure 8 for details of the input wiring see Figure 11 OUT A OUT B OUT C OUT D OUT A OUT B OUT C OUT D OUT A OUT B OUT C OUT D 470 1 W Ω Rs Rp Rp please order separately ORDER NO S54312 F7 A1 100 1 W Ω ONLY OPEN MONITORING ONLY OPEN MONITORING a b a b a b a b a b a b a b a b a b a b a b a b UL864 CLASS STYLE B B UL...

Page 8: ...27 chapter EOL Devices The EOL Resistors must be connected at the end of the input lines No addressable device or 2 wire smoke detectors can be connected to the inputs ACCESSORIES DEVICE ORDER NO EOL resistor 100 Ω 1 W S54312 F7 A1 SIEMENS INDUSTRY INC 4 11 16 inch adapter plate optional M 411000 RANDL INDUSTRIES INC 5 inch Box optional T55017 RANDL INDUSTRIES INC 5 inch Box optional T55018 RANDL ...

Reviews: