PROGRAMMING INSTRUCTIONS

Refer to Figure 3 to locate the opening on the
cage cover that allows access to the programming
holes which are on the FDCIO422 printed circuit
board.
To connect the FDCIO422 to the DPU or 8720
Programmer/Tester, insert the plug from the
DPU/8720 cable provided with the
Programmer/Tester into the opening on the front
of the FDCIO422. Be sure to insert the locating
tab on the plug into the slot for the locating tab as
shown in Figure 3. Minimum Firmware revision of
the DPU must be 9.00.0004, for 8720 must be
5.02.0002.

NOTICE

To prevent potential damage to the DPU
(refer to manual P/N 315-033260) or to
the 8720 (refer to manual P/N 315-
033260FA) DO NOT connect a FDCIO422
to the DPU or 8720 until the cage is
removed from the carrier (Figure 2).

Figure 3 Connecting the DPU/8720 plug to the cage

Modul Status LED

Flash Color

Condition

Flash Intervals

(Seconds)

Green*

Normal supervisory operation.

10

Amber

Device is in trouble

4

Red

Locate / Alarm

1

Input/Output active

10

No Flashes Device is not powered, or

replacement is needed.

-

* LED can be turned off. Please follow the corresponding

description of the Panel used.

WIRING

Refer to Figure 11. Refer to the appropriate wiring diagram and wire the addressable input/output module
accordingly.

Recommended wire size:

18 AWG minimum  and  14 AWG maximum
Wire larger than 14 AWG can damage the connector.

(Refer to Figures 2

 and

3). Follow the instructions in the DPU manual or 8720 manual to program the

FDCIO422 to the desired address. Record the device address on the label located on the front of the
module. The FDCIO422 can now be installed and wired to the system.

              Figure 4 Wiring multiple switches

INPUT NOTES:

1. There can be any number of normally open dry contact switches.
2. The end of line device must be located at the last switch.
3. Do not wire a normally closed switch across the end of line device in a normally open wiring.
4. Multiple switches: for open wiring supervision only.

INPUT ACTIVE LED,
red

INPUT TROUBLE LED,
yellow

PLUG FROM  DPU/8720
PROGRAMMER/TESTER

LOCATING
TAB

OUT A

OUT B

OUT C

OUT D

IN 1
IN 2
IN 3
IN 4

IN 1 trouble
IN 2 trouble
IN 3 trouble
IN 4 trouble

SLOT  FOR
LOCATING TAB

PROGRAMMING
HOLES

OUTPUT ACTIVE LED,
red

1)

1)

 Command for the activation

of the output received by the
control unit

PROGRAMMABLE SWITCHES (SEE NOTES 1, 2 AND 3)

PROGRAMMABLE SWITCHES (SEE NOTES 1 AND 3)

Rp  

½ 

W

470

Ω

EOL

UL 864 CLASS    STYLE

B

B

UL 864 CLASS    STYLE

A

D

IN 1-4

IN1/IN2

IN3/IN4

Summary of Contents for FDCIO422

Page 1: ...ing type form A relay contacts for fire control installations Status indication per LED for each input and output plus 1 LED for general status of the device Power supply via FDnet supervised power limited Including 4 EOL devices 470 Ω 3 separators to separate the power limited wiring from the non power limited Separators are delivered in 3 different sizes for standard 4 11 16 inch box 4 11 16 inc...

Page 2: ...se follow the corresponding description of the Panel used WIRING Refer to Figure 11 Refer to the appropriate wiring diagram and wire the addressable input output module accordingly Recommended wire size 18 AWG minimum and 14 AWG maximum Wire larger than 14 AWG can damage the connector Refer to Figures 2 and 3 Follow the instructions in the DPU manual or 8720 manual to program the FDCIO422 to the d...

Page 3: ...n power limited fire protection signaling conductors For the FDCIO422 wiring to the terminal block for line and inputs must enter the outlet box separately from the terminals for outputs For the output terminals protection with a fuse is recommended Refer to Figures 6 and 9 WIRING AT THE TERMINAL BLOCKS Minimize the length of wire entering the outlet box Figure 6 Power Limited Wiring Separators Th...

Page 4: ...se the module without the faceplate Remove the faceplate for service and maintenance reasons only Figure 7 Mounting the FDCIO422 TECHNICAL DATA Operating voltage DC 12 32 V Operating current quiescent 1 mA Absolute maximum peak current 1 92 mA Maximum current connection factor 2 4 Relays output 1 normally open normally closed DC 30 V AC 125 V Max 4x 5 A or 2x 7 A OUT B C or 1x 8 A OUT C Operating ...

Page 5: ...ptable means Insulate shields do not make any connections to the device or back box 16 Use shielded and or twisted wire to connect the switch wiring and keep the wiring as short as possible 17 Tie the switch wiring shield to the local earth ground at only one end refer to Figure 9 For multiple switches on the same input connect incoming and outgoing shields together in an acceptable means Insulate...

Page 6: ...l Remedy cause Note Any general message can be displayed together with another status Configuring the outputs Configuring the inputs For configuring the outputs proceed as follows a Determine in which position the contact is active The contact can be active when it is Closed normally open NO Open normally closed NC b After activating the contact remains Permanently active Active only for a certain...

Page 7: ...10 FDCIO422 input wiring Class A and Class B for details of Line 1 and 2 wiring see Figure 8 for details of the input wiring see Figure 11 OUT A OUT B OUT C OUT D OUT A OUT B OUT C OUT D OUT A OUT B OUT C OUT D 470 1 W Ω Rs Rp Rp please order separately ORDER NO S54312 F7 A1 100 1 W Ω ONLY OPEN MONITORING ONLY OPEN MONITORING a b a b a b a b a b a b a b a b a b a b a b a b UL864 CLASS STYLE B B UL...

Page 8: ...27 chapter EOL Devices The EOL Resistors must be connected at the end of the input lines No addressable device or 2 wire smoke detectors can be connected to the inputs ACCESSORIES DEVICE ORDER NO EOL resistor 100 Ω 1 W S54312 F7 A1 SIEMENS INDUSTRY INC 4 11 16 inch adapter plate optional M 411000 RANDL INDUSTRIES INC 5 inch Box optional T55017 RANDL INDUSTRIES INC 5 inch Box optional T55018 RANDL ...

Reviews: