3

Building Technologies

A6V10257736_d_--_--

Fire Safety

2018-12-20

en

Installation

Use

Alarm indicators provide optical repeat signals for
automatic fire detectors.

FDAI91 (Fig. 1) for frame mounting

FDAI92 (Fig. 4) for surface mounting

FDAI93 (Fig. 12) for installation in door frames,
switchboards, false ceilings or special housings

Installing FDAI91 on door frames

For master gauge for holes in door frame, see Fig. 2.

1.

Drill up to 4 holes, ø max. 7.5 mm in the door frame
for cable entries as required.

2.

Remove white cover cap (snap out).

3.

Attach alarm indicator base plate (Fig. 3) to door
frame with two screws, ø max. 3 mm.

4.

Connect alarm indicator in accordance with
connection diagram (Fig. 6).

5.

Refit white cover cap.

6.

Snap the white cover cap into place.

Surface-mounted installation of FDAI92

1.

Remove the white cover cap (press the black cam).

2.

Mount the base plate (Fig. 5) on a wall or recess-
mounted socket using 2…4 screws with
max. diameter 3 mm.

3.

Connect alarm indicator in accordance with
connection diagram (Fig. 6).

4.

Refit the white cover cap.

5.

Snap the white cover cap into place.

Adapter frame AI330 for FDAI92

For surface-mounted cable entry the additional frame
AI330 (accessory) must also be mounted.
Max. cable diameter: 10 mm

1.

Mount the additional frame AI330 on a wall or
recess-mounted socket using two screws,
ø max. 4 mm (Fig. 7, Fig. 8).

2.

Attach alarm indicator FDAI92 to adapter frame
AI330 with 2 wood or sheet metal screws, ø 3 mm,
max. 16 mm long.

Line connections FDAI91 and FDAI92 (Fig. 9)

1.

Strip approx. 7...8 mm of insulation from connection
wires.

2.

Insert wires in spring clips [3].

3.

To insert thinner wires or release trapped wires:
Use a screwdriver or other suitable tool to press
down the relief [4] of the spring clip.

Connecting to automatic fire detector (Fig. 10,
Fig. 11, Fig. 21)

Connect alarm indicator FDAI91, FDAI92 or FDAI93 in
accordance with the connection diagram shown.
Select the appropriate connection diagram depending
on the installed detector family.
Observe the information in the detector documentation.

Installation of FDAI93 in frames (Fig. 15) and ceiling
panels (Fig. 16)

1.

Make a hole, ø 22,5 mm, at the installation site.

2.

Slide insulating cap [6] on to connection wires.
(Fig. 12)

3.

Connect alarm indicator FDAI93 in accordance with
connection diagram (Fig. 14).

4.

Slide insulating cap [6] on to alarm indicator until
screw terminals [7] are covered.

5.

Push alarm indicator FDAI93 into hole.

Surface-mounted housing DCA1191 (Fig. 19) and
indicator housing DJZ1193 (Fig. 20) for FDAI93

When using alarm indicator FDCAI93 in wet areas,
surface-mounted housing DCA1191 (accessory) or
indicator housing DJZ1193 (accessory) must also be
fitted.
Max. four alarm indicators FDAI93 can be fitted in the
surface-mounted housing DCA1191. The necessary
installation holes of ø 22.5 mm must be made by the
customer.
The indicator housing DJZ1193 has the installation
hole for installing an alarm indicator. A washer is
supplied.

1.

Use two screws of ø 3.5 mm to fit the housing on a
plane surface (Fig. 17, Fig.  20).

2.

Fit alarm indicator FDAI93 in a drilled hole of
ø 22.5 mm. Always use a washer [8] between the
collars of FDAI93 and housing cover (Fig. 18,
Fig. 20).

3.

Screw housing cover down to housing (Fig. 19,
Fig. 20).

Line connection FDAI93 (Fig. 13)

1.

Strip approx. 7...8 mm of insulation from connection
wires.

2.

Insert wires into screw terminals [7].

3.

Tighten screw terminals [7].

Summary of Contents for FDAI91

Page 1: ...ndicateur d action joint compris es Indicadores de alarma marco suplementario carcasa para montaje en superficie carcasa del indicador junta incl it Indicatori di allarme quadro supplementare contenitore a parete contenitore dell indicatore incl guarnizione 24 12 6 7 5 12 6 7 5 7 5 32 47 8 37 3 5 en Installation de Montage fr Montage es Montaje it Montaggio Fig 1 Fig 2 Fig 3 28 56 85 60 56 3 5 Fig...

Page 2: ...ier Bloque de terminales Morsettiera 3 Spring clips Federklemmen Clips à ressort Terminales elásticos Clip a molla 4 Relief for spring clip Entlastung Federklemme Décharge clip à ressort Alivio del terminal elástico Fermacavo anti trazione clip a molla 5 Detector Melder Détecteur Detector Rivelatore 6 Insulating cap Isoliertülle Capuchon isolant Manguito aislante Isolatore passante 7 Screw termina...

Page 3: ...ing clips 3 3 To insert thinner wires or release trapped wires Use a screwdriver or other suitable tool to press down the relief 4 of the spring clip Connecting to automatic fire detector Fig 10 Fig 11 Fig 21 Connect alarm indicator FDAI91 FDAI92 or FDAI93 in accordance with the connection diagram shown Select the appropriate connection diagram depending on the installed detector family Observe th...

Page 4: ...der bereits eingeklemmte Drähte zu lösen Drücken Sie mit einem Schraubendreher oder einem anderen geeigneten Werkzeug auf die Entlastung 4 der Federklemme Anschluss an automatische Brandmelder Fig 10 Fig 11 Fig 21 Schließen Sie den Alarmindikator FDAI91 FDAI92 oder FDAI93 gemäß dem dargestellten Anschluss schema an Je nach installierter Melderfamilie ist das zugehörige Anschlussschema zu wählen Be...

Page 5: ... défaire des câbles déjà insérés Appuyez sur la décharge 4 du clip à ressort à l aide d un tournevis ou d un autre outil adapté Raccordement sur détecteur d incendie automatique fig 10 fig 11 fig 21 Raccordez l indicateur d action FDAI91 FDAI92 ou FDAI93 conformément le schéma de raccordement représenté Selon la famille de détecteurs installés il faut sélectionner le schéma de raccordement corresp...

Page 6: ...r hilos fijados Presione con un destornillador u otra herramienta adecuada sobre el alivio 4 del terminal elástico Conexión a detectores automáticos de incendio Fig 10 Fig 11 Fig 21 Conecte el indicador de alarma FDAI91 FDAI92 o FDAI93 de acuerdo con el diagrama de conexión representado Dependiendo de la familia de detectores instalada deberá seleccionarse el diagrama de conexión correspondiente O...

Page 7: ... 11 Fig 21 Collegare l indicatore di allarme FDAI91 FDAI92 o FDAI93 alla linea di rivelatori secondo lo schema di collegamento raffigurato A seconda della famiglia di rivelatori installata deve essere selezionato lo schema di collegamento appartenente Osservare le istruzioni presenti nella documentazione del rivelatore Montaggio FDAI93 in telai Fig 15 e solette del soffitto Fig 16 1 Praticare un f...

Page 8: ...ueidad incl it Contenitore dell indicatore incl anello di guarnizione Siemens Schweiz AG Theilerstrasse 1a CH 6300 Zug Technical data see doc A6V10257736 09 FDAI91 Alarm indicator for use in fire detection and fire alarm systems installed in buildings 2014 30 EU EMC EN 50130 4 EN 61000 6 3 2011 65 EU RoHS EN50581 The declared conformity can be seen in the EU Declaration of Conformity DoC which is ...

Reviews: