DACT Compatible Alarm Communicators
The FC901-U3/-R3 DACT is also compatible with Alarm communicators that utilized different
communication technologies (IP and GSM technologies) to connect to compatible Receivers
using compatible protocol listed within this documentation.
COMPATIBLE ALARM COMMUNICATORS
Manufacturer
Model
Number
Communication
Technology
Installation
Part Number
Tellular
TG7GFS04
GSM
56044102
Bosch
C900V2
IP
F01U087780-01
DSC
TL300CF
IP
29007636/29007842
DSC
3G370-CF
GSM
29008179
NOTE:
DACT is configured with the alarm communicator for other transmission
technologies, off-premise signaling for UL. DACT is used for off-premise signal
transmission for ULC.
When using these alarm communicators, the DACT shall be configured for
Contact ID.
Refer to the Alarm Communicator Installation Instruction for compatible
receivers.
Wiring between the DACT and the alarm communicator shall be within 20 feet,
and in conduit.
The C900V2 shall be installed in accordance with its installation instructions.