BATTERY SIZE CALCULATIONS
System Current Draw Break down
System Current Draw Components
Standby(A)
Alarm(A)
Main board
0.1590
0.1864
NAC
0
C1
SLC
C2
C3
Auxiliary power
C4
C5
City tie module
0.0017
0.0158
SLC Current Draw Break down
SLC Current Draw Components
Standby(A)
Alarm(A)
HFP-11 / 8713
0.00140
0.00140
HFPO-11 / 8710
0.00140
0.00140
HFPT-11 / 8712
0.00140
0.00140
OOHC941
0.00075
0.00075
OOH941
0.00068
0.00068
OH921
0.00030
0.00030
OP921
0.00030
0.00030
HI921
0.00028
0.00028
FDCIO42
0.00120
0.00120
HMS / 8700 -S/D/M
0.00140
0.00140
HTRI-S / 8702
0.00140
0.00140
HTRI-D / 8703
0.00140
0.00140
HTRI-R / 8704
0.00140
0.00140
HZM / 8705
0.00140
0.00140
HCP /8706
0.00140
0.00140
ILED / 8726
0.00140
0.00140
FDOOTC441
0.00075
0.00075
FDOOT441
0.00068
0.00068
FDOT421
0.00030
0.00030
FDO421
0.00030
0.00030
FDT421
0.00028
0.00028
ABHW-4B
0.00030
0.00030
ABHW-4S
0.00030
0.00030
Total Standby Current = 0.1590 + C2 + C4 + 0.0017(if used)
Total Alarm Current = 0.1864 + C1 + C3 + C5 + 0.0158(if used)
Where
C1 = NAC1 c NAC2 current, should be less or equal to 2.5A.
C2 = ∑quantity of each type of detector x standby current/each
C3 = ∑quantity of each type of detector x alarm current/each
C4 = External device current draw through Aux1 and Aux2 in standby stage, either one of
Aux1 and Aux2 should be less than or equal to 0.75A.
C5 = External device current draw through Aux1 and Aux2 in alarm stage, either one of Aux1
and Aux2 should be less than or equal to 0.75A.