Wiring and interfaces
ECOFAST Motor Starters
GWA 4NEB 950 0562-12
3-5
Deutsc
h
Eng
lish
3.2
Wiring rules
Warning
Hazardous voltages! These may cause electric shock and burns.
Disconnect the system and device from the supply before starting work.
3.2.1
Selecting the power leads
The core cross-section of the power leads must be matched to the respective
ambient conditions. The decisive factors for choosing the core cross-section are
as follows:
• set current on the device
• method of installation
• ambient temperature
• type of material (PVC, rubber)
For PVC power leads installed in a cable duct, for example, the maximum cur-
rent carrying capacity as a function of ambient temperature is as follows:
Observe the following rules when carrying out wiring:
Table 3-1: Rules for wiring
30 °C
40 °C
45 °C
50 °C
55 °C
1.5 mm
2
14 A
12.2 A
11.1 A
9.9 A
8.5 A
2.5 mm
2
19 A
16.5 A
15.0 A
13.5 A
11.6 A
4.0 mm
2
26 A
22.6 A
20.5 A
18.5 A
15.9 A
Rules for flexible cables
Data
Current carrying capacity of the plug connection as a
function of the connectable core cross-sections and ambi-
ent temperature
T
u
=
55 °C
40 °C
1.5
mm
2
2.5 mm
2
4.0 mm
2
12 A
20 A
30 A
15 A
25 A
35 A
Permissible outer diameter of the cable
sealing insert
green
red
white
7.0 ... 10.5 mm
9.0 ... 13.0 mm
11.5 ... 15.5 mm
Length of insulation to strip from cores
8 mm
Length of insulation to strip from cable sheath
20 mm
T
U
Ø
Summary of Contents for ECOFAST
Page 1: ...Part ofTotally Integrated Automation ecofast 02 2002 Motor Starter ...
Page 7: ...ECOFAST Motor Starters iv GWA 4NEB 950 0562 12 ...
Page 9: ...ECOFAST Motor Starters vi GWA 4NEB 950 0562 12 ...
Page 17: ...Motor Starters Overview ECOFAST Motor Starters 1 6 GWA 4NEB 950 0562 12 ...
Page 25: ...Installation of Motor Starters ECOFAST Motor Starters 2 8 GWA 4NEB 950 0562 12 ...
Page 55: ...Device functions ECOFAST Motor Starters 5 6 GWA 4NEB 950 0562 12 ...
Page 75: ...ECOFAST Motor Starter Index 2 GWA 4NEB 950 0562 12 ...
Page 77: ...Correction page ECOFAST Motor Starters GWA 4NEB 950 0562 12 ...