Performance Data
B3–15
CP 443-5 Basic for PROFIBUS / Manual Part B3 –
Release 11/2002
C79000-G8976-C161-03
Further Notes on FMS
Please note the following:
S
This version of the CP supports FMS broadcast.
S
Access to variables with password protection or group permissions is not
supported with the PC acting as an FMS client.
Note
Refer also to the entry at the following Internet address:
http://www4.ad.siemens.de/view/cs/de/10535180
S
When reloading configurations with large numbers of connections in the
RUN mode, the following reactions may result:
– You receive the error message “Storage medium not obtainable”. The new
configuration data are not accepted.
– When diagnostics is called, it is possible that no diagnostic information is
displayed.
You can avoid this reaction by downloading the configuration data to the CP
in the STOP mode.
S
Startup of the CPU after Power On
In the Properties dialog of the CPU, set the ”Startup after power on” to “Warm
restart” or “Cold start”.
Note
You should also refer to the entry on FMS data structures at the following Internet
address:
http://www4.ad.siemens.de/view/cs/de/10347267