Compatibility with the Previous Product
B3–21
CP 443-5 Basic for PROFIBUS / Manual Part B3 –
Release 11/2002
C79000-G8976-C161-03
6.2
Replacing Older Modules / Replacing Defective Modules
Replacing Modules
Please follow the following procedure when replacing an older module with one of
those described here:
Table 6-1
Module used until now
Configuration Procedure
6GK7 443-5FX00-0XE0
Configuration unchanged (replacing a defective module)
If you have no extra requirements for the CP compared with the old
one, no changes to the configuration are necessary.
Then you only need to remember the following difference when using
the CP:
S
Download the configuration data from your PG/PC to the CP
again.
Extending the Configuration (using new functions)
If you want to use the extended functions of the new CP, follow the
steps outlined below (see also Chapter 3):
1. In STEP 7 / HW Config replace the already configured CP 443-5
Basic with the new module; you will find this in the Hardware
Catalog.
2. Modify your configuration according to your requirements, for
example in the Properties dialog for the PROFIBUS subnet.
3. Save, compile, and download the configuration data to the CPU
or the CP.
Information in the NCM S7 for PROFIBUS Online Help and Documentation
The information “for new modules” contained in both the STEP 7 / NCM S7 online
help and the NCM S7 for PROFIBUS manual is also relevant for the CP described
here. Look out for this symbol.