Error Word
Transfer Rou-
tine
Hex Dec
Error Byte
Reaction/Correction
Byte
Offset
in SM
Area
Return
Value
(ETHx_)
16#003A
58
The module name for the CP
243-1 IT was changed in the
configuration.
Check the configuration.
20, 21 _CTRL
16#003B
59
The configuration has an invalid
IP address.
Check the configuration.
20, 21 _CTRL
16#003C
60
The configuration has an invalid
gateway address.
Check the configuration.
20, 21 _CTRL
16#003D
61
The configuration has an invalid
value in the Keep Alive parame-
ter.
Check the configuration.
20, 21 _CTRL
16#003E
62
No valid configuration received
from memory or S7-200 CPU or
via BOOTP
Cyclic attempt to obtain a
valid configuration either from
the memory of the S7-200
CPU or via a BOOTP server
20, 21 _CTRL
16#0042
66
The NDB contains syntax mis-
takes in the read/write jobs or
lengths.
Check the configuration.
20, 21 _CTRL
16#0093
147
The BOOTP job failed.
Automatic restart
20, 21 _CTRL
16#0094
148
The reply of the BOOTP server
contains invalid data.
Automatic restart
20, 21 _CTRL
16#0095
149
The TCP/IP stack did not ac-
cept the specified monitoring
time (Keep Alive).
Automatic restart
20, 21 _CTRL
16#0096
150
The TCP/IP stack did not ac-
cept the IP address specified
for a client.
Automatic restart
20, 21 _CTRL
16#0097
151
The TCP/IP stack did not ac-
cept the specified subnet mask.
Automatic restart
20, 21 _CTRL
16#0098
152
The TCP/IP stack did not ac-
cept the specified gateway ad-
dress.
Automatic restart
20, 21 _CTRL
16#00B0
176
The IDB contains invalid val-
ues.
Prepare configuration with
STEP 7 Micro/WIN 32.
20, 21 _CTRL
16#00B1
177
The CRC check of the IDB
failed.
Prepare configuration with
STEP 7 Micro/WIN 32.
Check the user program to
see whether configuration
data were accidentally over-
written.
20, 21 _CTRL
16#00B2
178
No administrator name is speci-
fied in IDB.
Prepare configuration with
STEP 7 Micro/WIN 32.
20, 21 _CTRL
Summary of Contents for CP 243-1 IT
Page 46: ...Installation and Commissioning 03 03 CP 243 1 IT J31069 D0429 U001 A0 7618 46 ...
Page 94: ...Programming 03 03 CP 243 1 IT J31069 D0429 U001 A0 7618 94 ...
Page 106: ...Diagnosis 03 03 CP 243 1 IT J31069 D0429 U001 A0 7618 106 ...
Page 120: ...Technical Data 03 03 CP 243 1 IT J31069 D0429 U001 A0 7618 120 ...
Page 130: ...Example 03 03 CP 243 1 IT J31069 D0429 U001 A0 7618 130 ...