DIP switch settings
If the bus address is set for
CerPass reader protocol
,
the reader addresses
1 . . . 16
can be used.
If the bus address is set for
UCI reader protocol
,
only the reader addresses
1 . . . 4
can be used.
The method of address counting and addressing (number of readers to be connected) depends on the
controller / reader interface used and must be taken into account.
7.2
Setting the address (Clock/Data)
There is no need to select a reader address when the Clock/Data interface is used.
The Clock/Data interface allows only one reader to connect with the interface.
7.3 Communication
interface and protocol selection
The communication interface has to be selected either to communicate with
intelligent controllers or via RS485 bus to connect to a reader interface or
Clock/Data interface.
Within the communication interface there are different protocols selectable.
DIP 4 DIP 5 DIP 6 Communication interface
Protocol
x
off
off
RS485 bus operation
UCI reader protocol
x off
on
RS485 bus operation
CerPass reader protocol
off
on
off Clock/Data
interface
Wiegand
on on
off
Clock/Data interface
Omron (Magstripe Track II)
x
on on
RS485 point-to-point
Configuration mode
x – don’t care, see tab. 2
Tab. 3
Selection of communication interface
Note:
In RS485 bus operation, DIP 4 is LSB of the reader's bus address.
15
Siemens Building Technologies
Fire & Security Products
12.2004