2.4.2.11/2

Technical Data

Physical Specifications

housing: plastic

dimensions:

Length x Width x Height  (in mm): 180 x 50 x 41,1

weight: approx. 100g

fire load: approx. 3000 kJ

mounting: with two screws

one mounting location for RS / RL modules

Connections

Bus line: screwless bus connection block (red-black)
0.6…0.8 mm Ø single core, strip insulation 5mm

Mains power: 230 V AC ± 10 %, 50...60 Hz
terminals of RS / RL modules

Electrical Safety

Degree of pollution (according to IEC 60664-1): 2

Type of protection (according to EN 60529): IP 20

Overvoltage category (according to IEC 60664-1): III

Bus: safety extra low voltage SELV DC 24 V

Environmental specifications

Climatic withstand capability: EN 50090-2-2

Ambient temperature operating: - 5 ... + 45

C

Ambient temperature non-op.: - 25 ... + 70

C

relative humidity (non-condensing): 5 % bis 93 %

CE norm

complies with low voltage regulations

Mounting and Connecting

General description
The Control Module Box is designed for on-surface
mounting on ceilings, walls, on the floor or any even
surface, as well as installation in installation channels or
raceways. The holes for screw fastening of the Control
Module Box are located on the ends of the box and are
accessible after opening the housing. The Control Mod-
ule Box is affixed with two screws.

Mounting

Mounting of the Control Module Box:

- Distance between drill holes for screw fastening:

166 mm    (see figure 2-a)

- Pull the latching clamp (A4) away from the lid (A5), lift

the lid up, swivel it up and remove it from the hinge
(A6).

- Fix the Control Module Box at the fixation points (A2)

(see figure 2-b) with screws (e.g. 4.5 x 50 mm, to be
sourced separately).

figure 2a: Mounting

Summary of Contents for AP 118

Page 1: ...tuator 2 x 6A 5WG1 525 2AB23 Universal dimmer 1 x 250VA The mounted module is connected to the bus line via a bus terminal block The AP 118 Control Module Box provides wiring space with room for two connectors for PE and N conductors This allows for secure connection of the PE and N con ductors of the cables inserted into the AP 118 Control Module Box For strain relief cables can be secured at the...

Page 2: ... category according to IEC 60664 1 III Bus safety extra low voltage SELV DC 24 V Environmental specifications Climatic withstand capability EN 50090 2 2 Ambient temperature operating 5 45 C Ambient temperature non op 25 70 C relative humidity non condensing 5 bis 93 CE norm complies with low voltage regulations Mounting and Connecting General description The Control Module Box is designed for on s...

Page 3: ...separately A14 Clamp for strain relief cut off from base A2 A14 A7 A6 A11 A9 A4 A2 A14 A8 figure 2b Mounting Removing the lid of the Control Module Box Remove the screws A3 securing the lid Pull the latching clamp A4 away from the lid A5 lift the lid up swivel it up and remove it from the hinge A6 Mounting the lid of the Control Module Box Hook the lid A5 into the hinge A6 Push the lid A5 down unt...

Page 4: ... with 0 6 0 8 mm Ø B13 Hinge joint for mounting hinge of the RL module B14 Terminals Mounting of a RS module AP 118 Remove the lid of the Control Module Box Insert the bus connection module B5 in such a way into the insertion point B6 for the bus connection module that the bus connection pins B10 point to the insertion point for the bus terminal B11 Press the bus connection module B5 down until it...

Page 5: ...he bus terminal B12 To remove the RL module B2 insert a screw driver between the module and the mounting location on the bus terminal side and push it up to release it from the snap in hooks Swivel the RL module B2 up pull it down out of the hinge B13 and remove it from the mounting location B4 Mount the lid again figure 8 dismounting an RL module Wiring Slipping off on bus connection blocks The b...

Page 6: ...uits are connected via screwless plug in terminals E1 Remove approx 9 10 mm of insulation from the wire E 1 1 and plug it into the terminal E1 The terminals are designed for connection of two wires allowing to loop through the terminal block Note The maximum permissible terminal load current is 16A Remove wires Press the terminal interlocking of the terminal F1 with a screw driver and remove the w...