Fire Safety
2017.09.07
RENOVATION
What is the pur-
pose of the
'Renovation'
operating
mode?
The 'Renovation' operating mode is a special function of interactive detectors of the DO and
DOT type and is only available at 'ZONE' level.
When in 'Renovation' operating mode,
interactive automatic detectors
have
much less sensitivi-
ty
. This may be required when carrying out extraordinary work (e.g. when renovating a building).
The fire detection installation continues to work; the remote transmission of alarm and error
messages is not blocked.
i
The behaviour in 'Renovation' operating mode are as follow:
Smoke
Temperature
Interaktiv
DO1151/52
200s delayed.
-
DO1153
30-45s delayed.
DOT1151/52 unchanged
+25°C/min or 82 °C
Sinteso
FDO
switched off
-
FDT
-
80 °C, at least 20 sec pending
FDOOT
-
80 °C, at least 20 sec pending
F
see also documents 1009, 1040, 1027, 7004
Detectors in 'Renovation' operating mode are considered to be out of action from an insurance
and approval standpoint. A message of the 'Isolation' category is therefore generated.
Manual call points function as in normal operation.
Operating ac-
cess
If you still don't have operating access when starting operation work, the release procedure is
automatically called up.
Switching
'Renovation'
operating mode
on/off for a de-
tector
Perform the following steps to set one detector zone to 'Renovation' operating mode:
Step
Action
Result / Comment
1
Navigate
to the ZONE you want using:
<Operate..>
t
<Browse..>
t
<Browse FIRE DETECTION..>
- or -
<Browse EXTINGUISHING..>
t
<Select SECTION
¯
>
t
<Select ZONE
¯
>
The zone functions are displayed