Operating instructions
Œ•Ž
19
Building Technologies
A6V10225450_b_en_--
Fire Safety
2017.09.07
Step
Action
(continued)
4
Poll
·
Intervention text
•
(if present)
·
Elements in alarm
•
(if present)
5
Read fire location
on the display
6
Go to
the indicated
fire location
7
Decide whether 'Major incident' or 'Minor incident':
Major incident
IF
Fire brigade
already informed
8
THEN
·
Attempt to rescue people
·
Guide fire brigade to fire location
·
Tackle fire
IF
Countdown running
8
THEN
Immediately activate nearest
manual call point
- or - (only available with B3Q661)
Press
<Alarm delay off> button
‘
IF
No transfer
to fire brigade
8
THEN
Phone fire brigade
Minor incident
IF
Fire brigade
already informed
8
THEN
·
Try to stop fire brigade
·
Press
<Reset> button
’
Õ
The system returns to 'Normal operation'
IF
Countdown running
8
THEN
Press
<Reset> button
straightaway
’
Õ
The system returns to 'Normal operation'
IF
No transfer
to fire brigade
8
THEN
Press
<Reset> button
’
Õ
The system returns to 'Normal operation'
NOTE:
·
The password has to be entered to reset the system.
·
The room may have to be aired before you can reset the system.
·
Zones which cannot be reset, can be temporarily switched off by pressing the
<isolate detector zones in ALARM>
softkey
Summary of Contents for AlgoPilot B3Q661
Page 84: ......