6 The settings in detail
2014-07-30
By changing the value entered, the respective heating periods will be shortened or
extended.
Increase:
Heating mode will start
earlier,
changeover to ECO
later.
Decrease: Heating mode will start
later,
changeover to ECO
earlier.
·
The function is not active in operating mode ”Continuously Comfort temperature“
·
The display will show ECO
·
To give consideration to the building’s thermal dynamics, the outside temperature will
be attenuated
Flow temperature setpoint limitations
Line no.
Operating line
HC1
HC2
HCP
740
1040
1340
Flow temp setpoint min
741
1041
1341
Flow temp setpoint max
Using this limitation, a temperature range for the flow temperature setpoint can be
defined. If the flow temperature setpoint demanded by the heating circuit reaches the
relevant limit and heat request increases or decreases, the flow temperature setpoint
will be maintained at the maximum or minimum limit.
TVw
Current flow temperature setpoint
TVmax
Flow temperature setpoint maximum
Tvmin
Flow temp setpoint min
room influence
Line no.
Operating line
HC1
HC2
HCP
750
1050
1350
Room influence
Types of compensation:
When a room temperature sensor is used, there is a choice of 3 different types of
compensation.
Setting
Type of compensation
- - -
%
Pure weather compensation *
1…99 %
Weather compensation with room
influence *
100 %
Pure room compensation
* Outside sensor required
The flow temperature is calculated via the heating curve, depending on the composite
outside temperature.
This type of compensation calls for a correct adjustment of the heating curve since in
that case the control gives no consideration to the room temperature.
Pure weather
compensation
0 10 20 30 40 50 60 70 80 90 100
TV
max
min
akt
°C
2
3
5
8
Z
0
9
TVw
TVmin
TVmax