6 The settings in detail
2014-07-30
The floor curing function ensures controlled drying of the floor. It controls the flow
temperature in accordance with a certain temperature profile. Drying of the floor is
ensured via the floor heating system and the mixing or pump heating circuit.
Off:
Function is deactivated.
Functional heating
(Fh) :
The first part of the temperature profile is automatically completed.
Floor curing heating
(Bh)
The second part of the temperature profile is traversed automatically.
Functional and floor curing heating
The entire temperature profile (first and second part) is traversed automatically.
Floor curing heating and functional heating
The entire temperature profile (first and second part) is traversed automatically.
Manually
It is not a temperature profile that is completed, but the floor setpoint is controlled
manually.
·
Observe the relevant standards and regulations of the floor manufacturer!
·
Proper functioning is ensured only when the plant is correctly installed (hydraulic
system, electrical installation, settings)!
If not observed, the floor might get damaged!
·
The function can be aborted prematurely by choosing
Off
·
Maximum limitation of the flow temperature remains active
X
Start day
Fh
functional heating
Bh
floor curing heating
recooling
Line no.
Operating line
HC1
HC2
HCP
860
1160
1460
Recooling storage tank
The surplus heat stored in the heat exchanger can be drawn off by space heating. This
can be adjusted separately for each heating circuit. (Also refer to operating page “DHW
storage tank“, operating line “Recoolign boiler/HC“)
Floor curing function
50
45
40
35
30
20
5
10
15
18
[Tag]
0
25
55
Fh
Bh
1
1
5
7
X
Fh + Bh
1
25
2
3
5
8
Z
1
0
[TVw]