47/109
Siemens
User Manual
CE1U2357en
Building Technologies
5 Handling
2014-07-30
O
p
e
ra
ti
n
g
lin
e
U
s
e
r
le
v
e
l
F
u
n
c
ti
o
n
D
e
fa
u
lt
v
a
lu
e
M
in
M
a
x
U
n
it
5950 I
Function input H1
Optg mode change HCs+DHW ¦ Optg mode changeover
HCs ¦ Optg mode changeover HC1 ¦ Optg mode
changeover HC2 ¦ Optg mode changeover HCP ¦ Heat
generation lock ¦ Error/alarm message ¦ Min flow temp
setpoint ¦ Heat request ¦ Pressure measurement
Optg mode change
HCs+DHW
-
5951 I
Contact type H1
NC ¦ NO
NO contact
-
5952 I
Min flow temp setpoint H1
70
8
Tkmax
(120°C)
°C
5954 I
Heat request 10V H1
100
5
130
°C
5956 I
Pressure value 3.5V H1
5.0
0.0
10.0
bar
5960 I
Function
input
H2
Optg mode change HCs+DHW ¦ Optg mode changeover
HCs ¦ Optg mode changeover HC1 ¦ Optg mode
changeover HC2 ¦ Optg mode changeover HCP ¦ Heat
generation lock ¦ Error/alarm message ¦ Min flow temp
setpoint ¦ Heat request ¦ Pressure measurement
Optg mode change
HCs+DHW
-
5961 I
Contact type H2
NC ¦ NO
NO contact
-
5962 I
Min flow temp setpoint H2
70
8
TKmax
°C
5964 I
Heat request 10V H2
100
5
130
°C
5966 I
Pressure value 3.5V H2
5.0
0.0
10.0
bar
6097 F Sensor
type
collector
0
-20
20
°C
6098 F Readjustm collector
sensor
0
-3
3
°C
6100 F
Readjustm outside sensor
0.0
-3.0
3.0
°C
6110 F Time constant building
15
0
50
h
6120 F
Frost protection plant
Off ¦ On
On
-
6200 I Saving
sensors
No ¦ Yes
No
-
6205 F
Reset to default parameters
No ¦ Yes
No
-
6212 I
Check no heat source 1
-
0
199999
-
6215 I
Check no storage tank
-
0
199999
-
6217 I
Check no heating circuits
-
0
199999
-
6220 F
Software version
-
0
99.9
-
error
6710 I
Reset:alarm relay
No ¦ Yes
No
-
6740 F
Flow temp 1 alarm
- - -
- - -
/ 10
240
min
6741 F
Flow temp 2 alarm
- - -
- - -
/ 10
240
min
6743 F
Boiler temp alarm
- - -
- - -
/ 10
240
min
6800 F History
1
-
F Error code 1
-
0
255
-
6802 F History
2
-
F Error code 1
-
0
255
-
6804 F History
3
-
F Error code 1
-
0
255
-
6806 F History
4
-
F Error code 1
-
0
255
-
6808 F History
5
-