Revision 04 * INSTALLATION AND OPERATING INSTRUCTIONS 8BT2 * 881-4027.9
on the wall need to be done:
2.1.4.1. Outlet from the rear of the switchgear
Fig1. Wall opening for the transfer of hot gas pressure to the outside (from the rear of the switchgear)
To make this arrangement on the wall, the reference point is the related panel’s arrangement
as seen in fig1. The gap (X dimension) between lateral side of the switchgear and the wall is
important to identify the location of wall opening. The aisle at the back side of the switchgear
(Y dimension) determines the length of the outlet channel. It should be specified during the
order stage to be able to produce the suitable exhaust channels.
2.1.4.2. Outlet from the lateral side of the switchgear
“Z-detail”
Pressure relief flaps
“Z-detail”
“Z-detail”