English
68
C53000-B1174-C166-1
– Radiated Electromagnetic Interference
ANSI/IEEE Std C37.90.2
– Dampened oscillations
IEC 60694, IEC 61000–4–12
EMC tests for emitted interference
EN 50081–1 (generic standard)
(Type test)
– Radio noise voltage to lines
IEC–CISPR22 limit value B
– Radio noise field strength
IEC–CISPR 22 limit value Class B
– Voltage fluctuations
IEC 61000–3–3
Vibration and shock stress IEC 60255–21
and
IEC 60068
Shock stress on stationary deployment
– Vibration IEC 60255–21–1,
Class 1,IEC 60068–2–6
– Shock
IEC 60255–21–2, Class 2, IEC 60068–2–27
– Seismic vibration
IEC 60255–21–2, Class 2, IEC 60068–3–3
Vibration and shock stress
IEC 60255–21 and IEC 60068–2
During transport
– Vibration
IEC 60255–21–1, Class 2, IEC 60068–2–6
– Shock
IEC 60255–21–2, Class 1, IEC 60068–2–27
– Continuous shock
IEC 60255–21–2, Class 1, IEC 60068–2–29
Temperatures IEC
60068–2
– Recommended temperature during
–5 °C to +55 °C
operation
– Permissible temporary (transient)
operating temperature
–20 °C to +70 °C
– Limit temperatures during storage
–25 °C to +55 °C
– Limit temperatures for operation
–25 °C to +70 °C
Storage and transport of the device with factory packaging!
Humidity
Admissible humidity conditions
yearly average
≤
75 % relative humidity;
on 56 days per year up to 93 % relative
humidity;
during operation, condensation not
permissible!
All devices shall be installed so that they are not exposed to direct sunlight, nor subject to
great fluctuations in temperature that may cause condensation to occur.