1904 CRIT.ANGLE
Critical angle of charact. trip-curve by REF
110Ý
[ ] 110Ý
90 Ý
[ ] 90Ý
10 0 Ý
[ ] 10 0 Ý
120Ý
[ ] 120Ý
130Ý
[ ] 130Ý
19102nd HARMON
State of 2nd harmonic restraint
OFF
[ ] off
ON
[ ] on
1911 2nd HARMON
2nd harmonic contend in the REF-current
min. 10%
max. 80©©©©
1912 I REFmax 2
Limit IREFmax of 2nd harmonic restraint
min. 1.0I/In
max. 20.0
©©©©
1925 T-DELAY
Trip time delay of restricted earth fault
min. 0.00
s
max. 60.00/Ñ
©©©©
1927 T-RESET
Reset delay after trip has been initiated
min. 0.00
s
max. 60.00
©©©©
©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©
2100 BACK-UP OVERCURRENT TIME
2101 BACKUP O/C
State of back-up overcurrent protection
OFF
[ ] off
ON
[ ] on
BLOCK TRIP REL
[ ] Block trip relay
2103 I>>
Pick-up value for high current stage I>>
min. 0.10
I/In
max. 30.00
©©©©
2104 T-I>>
Delay time for I>> (definite time)
min. 0.00
s
max. 32.00/Ñ
©©©©
2111 CHARACT
Overcurrent time stage characteristic
DEFINITE TIME
[ ] Definite time
NORMAL INVERSE
[ ] Normal inverse
VERY INVERSE
[ ] Very inverse
EXTREMELY INVERS [ ] Extremely inverse
2112 I>
Pick-up value of overcurrent time stage I>
min. 0.10
I/In
max. 30.00
©©©©
2113 T-I>
Delay time for I> (definite time)
min. 0.00
s
max. 32.00/Ñ
©©©©
2114 Ip
Pick-up value of overcurrent time stage Ip
min. 0.10
I/In
max. 20.00
©©©©