$SSHQGL[
87
9
&*&
Reference Table for Functional Parameters 7UT51X
²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²
1000 PARAMETERS
©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©
1100 TRANSFORMER DATA
1102 UN WIND 1
Rated voltage of winding 1 of the transformer
min. 0.4
kV
max. 800.0
©©©©
1103 PN WIND 1
Rated apparent power of winding 1
min. 0.2
MVA
max. 5000.0
©©©©
1104 IN CT WIN1
Primary rated current of CT winding 1
min. 1
A
max. 100000
©©©©
1105 CT1 STARPT
Starpoint formation of CT winding 1
TOWARDS TRANSF. [ ] Towards transformer
TWDS.LINE/BUSBAR [ ] Towards line/busbar
1106 Io HANDLE
Processing of zero sequence current of wind. 1
Io-ELIMINATION
[ ] Io-elimination
Io-CORRECTION
[ ] Io-correction
WITHOUT
[ ] Without
1107 IN CT STP1
Prim. rated current of starpoint CT winding 1
min. 1
A
max. 100000
©©©©
1108 CT1 EAR-PT
Earth point formation of starpoint CT wind. 1
TOWARDS TRANSF. [ ] Towards transformer
TOWARDS EARTH
[ ] Towards earth
1121 VECTOR GR2
Vector group numeral of winding 2
min. 0
max. 11
©©©©
1122 UN WIND 2
Rated voltage of winding 2 of the transformer
min. 0.4
kV
max. 800.0
©©©©
1123 PN WIND 2
Rated apparent power of winding 2
min. 0.2
MVA
max. 5000.0
©©©©
1124 IN CT WIN2
Primary rated current of CT winding 2
min. 1
A
max. 100000
©©©©
1125 CT2 STARPT
Starpoint formation of CT winding 2
TOWARDS TRANSF. [ ] Towards transformer
TWDS.LINE/BUSBAR [ ] Towards line/busbar
1126 Io HANDLE
Processing of zero sequence current of wind. 2
Io-ELIMINATION
[ ] Io-elimination
Io-CORRECTION
[ ] Io-correction
WITHOUT
[ ] Without
www