The supervision is blocked as soon as a pickup of a protection function is detected within a protection function
group and the time delay of the supervision has not yet elapsed.
This subfunction also covers the situation of a low load with 3-phase measuring-voltage failure and closed
circuit breaker, because the circuit-breaker condition is also determined from the circuit-breaker auxiliary
contacts. The subfunction for detecting a 3-phase measuring-voltage failure (see chapter
) is not released in this situation, for example, because the current flow is too low.
This subfunction can be switched on or off separately using the
Switch-on 3ph. failure
parameter.
Application and Setting Notes
Parameter: Asym.fail. - time delay
•
Recommended setting value
(_:113) Asym.fail. - time delay
=
10.00 s
The
Asym.fail. - time delay
parameter allows you to set the time during which a system incident
detected after the occurrence of the unbalance resets the monitoring. This setting is important in the case of
weak infeed (current < 10 % of rated current) in order to give certain protection functions (such as distance
protection) more time for detecting system incidents. As long as the time delay runs, it is assumed that the
unbalance is due to a system incident.
As soon as the time has elapsed, the supervision assumes a measuring-voltage failure and seals in.
Siemens recommends using the default setting.
If you want the seal-in function to operate sooner or at once, you can reduce the time.
Parameter: Asym.fail.-DO on netw.flt.
•
Recommended setting value
(_:115) Asym.fail.-DO on netw.flt.
=
No
Parameter Value
Description
no
After elapse of the time delay the supervision function seals in. Even if the
system incident criterion is fulfilled, the protection functions concerned will
remain blocked.
This avoids an unselective tripping of the protection functions due to an
absence of the measuring voltage in the case of an unbalanced system inci-
dent.
This is the default setting.
yes
The seal-in function is switched off. The supervision drops out immediately
when a system incident is detected. With this setting, the unbalanced meas-
uring-voltage failure is only reported, and in the event of a double failure
(measuring-voltage failure and system incident in parallel), unselective trip-
ping is preferred.
Parameter: 3ph.fail. - VA,VB,VC <
•
Recommended setting value
(_:101) 3ph.fail. - VA,VB,VC <
=
5 V
The
3ph.fail. - VA,VB,VC <
parameter allows you to set the pickup value of the monitoring.
Siemens recommends using the default setting.
If you expect major disturbances acting upon the voltage inputs, you can increase this value. Increasing the
values makes the supervision more sensitive to 3-phase system incidents.
Parameter: 3ph.fail. - phs.curr.release
•
Recommended setting value
(_:102) 3ph.fail. - phs.curr.release
=
0.1 A
for I
rated
= 1 A or
0.5 A
for I
rated
= 5 A
The
3ph.fail. - phs.curr.release
parameter is used to define the phase current threshold above
which the monitoring is released.
Siemens recommends using the default setting.
9.3.2.6
Supervision Functions
9.3 Supervision of the Secondary System
SIPROTEC 5, Overcurrent Protection, Manual
1249
C53000-G5040-C017-8, Edition 07.2017
Summary of Contents for 7SJ82
Page 8: ...8 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 38: ...38 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 60: ...60 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 186: ...186 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 194: ...194 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 966: ...966 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1072: ...1072 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1236: ...1236 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1306: ...1306 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1370: ...1370 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1404: ...1404 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1576: ...1576 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1614: ...1614 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1634: ...1634 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...