3-Phase Measuring-Voltage Failure
Logic
[losymmet-190912-01.tif, 1, en_US]
Figure 9-7
Logic Diagram 3-Phase Measuring-Voltage Failure
Balanced Fault – VA, VB, VC <
A 3-phase measuring-voltage failure is detected if the following criteria are fulfilled simultaneously:
•
All 3 phase-to-ground voltages drop below the threshold value
3ph.fail. - VA,VB,VC <
•
A jump of the voltage (Signal
jump V
)
If these criteria are fulfilled and the monitoring is released and not blocked, the
3ph.failure-alarm
indica-
tion is output. When the voltage returns (even as 1-phase), the monitoring drops out.
Release by Phase Current
When all phase currents exceed the threshold value
3ph.fail. - phs.curr.release
the monitoring is
released.
Blocking in the Case of a System Incident
In the case of a 3-phase system incident, supervision must be blocked. The device detects a 3-phase incident
with a jump in the current. This change is detected via the internal signal
Jump I
or when the change in
current of a phase current exceeds the threshold value
3ph.fail. - phs.curr. jump
. The change in
9.3.2.4
Supervision Functions
9.3 Supervision of the Secondary System
SIPROTEC 5, Overcurrent Protection, Manual
1247
C53000-G5040-C017-8, Edition 07.2017
Summary of Contents for 7SJ82
Page 8: ...8 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 38: ...38 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 60: ...60 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 186: ...186 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 194: ...194 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 966: ...966 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1072: ...1072 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1236: ...1236 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1306: ...1306 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1370: ...1370 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1404: ...1404 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1576: ...1576 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1614: ...1614 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1634: ...1634 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...