Building Technologies
74 319 0617 0 a
17.04.2008
33/180
en
Parameter list
Line
Function, display
Factory setting
(Range)
Setting
Explanations, notes and tips
Block "Space heating"
61 Heating limit for
NORMAL heating
(ECO day)
17.0 °C
(--.- /
−
5.0…+25.0)
...................
°C
Setting --.- = function disabled
62 Heating limit for
REDUCED heating
(ECO night)
5.0 °C
(--.- /
−
5.0…+25.0)
...................
°C
Setting --.- = function disabled
63 Building time con-
stant
20 h
(0…50)
......................
h
Light = 10 h
Medium = 25 h
Heavy = 50 h
64 Quick setback
1
(0 / 1)
.........................
0 = no quick setback
1 = quick setback
65 Room temperature
source
A
(0 / 1 / 2 / 3 / A)
.........................
0 = no room temperature sen-
sor present
1 = room unit at terminal A6
2 = room temperature sensor at
terminal B5
3 = mean value of the two units
at terminals A6 and B5
A = automatic selection
66 Type of optimization
0
(0 / 1)
.........................
0 = optimization with room
model
1 = optimization with room tem-
perature sensor/room unit
(setting 0 only allows optimum
start control)
67 Maximum heating-
up time
00:00 h
(00:00…42:00)
......................
h
Maximum forward shift for
switching on before start of
occupancy
Setting 00:00 = optimization of
switching on disabled