Setting procedure
1. Only with analog adjustment of heating curve: Adjust the bar in agreement with the planning
documentation or according to local practice
2. Make settings on operating lines 1…41 (enduser)
3. Select plant type on operating line 51
4. Make the relevant settings in the following parameter list. All functions and operating lines
required for the selected plant type will be activated and can be set. All operating lines that
are not required are locked
5. Enter the values set in the table!
6. If required, set the service functions (independent of plant type)
7. Carry out the final work (locking of settings, etc.)
Commissioning and functional check
•
Specific operating lines for the functional check:
– 161 = simulation of outside temperature
– 162 = relay test
– 163 = sensor test
– 164 = test of H-contacts
•
If appears on the display: Interrogate operating line 50 to pinpoint error