WARNING
To comply with EU Directive 2014/34 EU (ATEX 114), UK-Regulation SI 2016/1107 or the
conditions of IECEx or CCC-Ex, the housing or cabinet must meet the requirements of at least
IP54 (according to EN/IEC 60529, GB/T 4208) in compliance with EN IEC/IEC 60079‑7, GB
3836.8.
WARNING
The equipment shall only be used in an area of not more than pollution degree 2, as defined in
EN/IEC 60664-1, GB/T 16935.1.
Safety notices when using according to FM
If you use the device under FM conditions you must also keep to the following safety notices in
addition to the general safety notices for protection against explosion:
WARNING
EXPLOSION HAZARD
The equipment is intended to be installed within an enclosure/control cabinet. The inner
service temperature of the enclosure/control cabinet corresponds to the ambient temperature
of the module. Use cables with a maximum permitted operating temperature of at least 20 °C
higher than the maximum ambient temperature.
WARNING
Wall mounting is only permitted if the requirements for the housing, the installation
regulations, the clearance and separating regulations for the control cabinets or housings are
adhered to. The control cabinet cover or housing must be secured so that it can only be opened
with a tool. An appropriate strain-relief assembly for the cable must be used.
WARNING
Wall mounting outside of the control cabinet or housing does not fulfill the requirements of the
FM approval.
Note
You must not install the device on a wall in hazardous areas.
Installation and removal
5.1 Safety notices for installation
SCALANCE W786-x
Operating Instructions, 12/2021, A5E03678337-14
31
Summary of Contents for 6GK5786-1FC00-0AA0
Page 8: ...Introduction SCALANCE W786 x 8 Operating Instructions 12 2021 A5E03678337 14 ...
Page 10: ...Safety notices SCALANCE W786 x 10 Operating Instructions 12 2021 A5E03678337 14 ...
Page 66: ...Maintenance and cleaning SCALANCE W786 x 66 Operating Instructions 12 2021 A5E03678337 14 ...
Page 82: ...Dimension drawings SCALANCE W786 x 82 Operating Instructions 12 2021 A5E03678337 14 ...
Page 84: ...Certification SCALANCE W786 x 84 Operating Instructions 12 2021 A5E03678337 14 ...