Instructions for fitting connectors, attachments and devices
2.3 Electrical networks
Passive network components
52
System Manual, 02/2013, C79000-G8976-C282-01
2.
Cut the braided shield approximately 10 mm from the edge of the outer sheath
and pull off the loose shield.
3.
Shorten the white-blue pair by approximately 3 mm to 32 mm
(to introduce the cable as shown in Figure 1–10).
–
Turn back the braided shield over the outer sheath.
–
Unwind the aluminum foil shield leaving approximately 15 mm (shorter pair) or
approximately 18 mm (longer pair) to the folded back braided shield and cut off the
unwound shield.
–
Remove the plastic foil and blind element.
–
Remove approximately 5 mm of the insulation from the conductors.
4.
Wrap copper band around the braided shield.