Instructions for fitting connectors, attachments and devices
2.3 Electrical networks
Passive network components
System Manual, 02/2013, C79000-G8976-C282-01
43
WARNING
Keep to the instructions in the SCALANCE W manual for fitting an IP67 hybrid cable
connector to a SCALANCE W device!
2.3.10.3
Fitting IE hybrid cable 2x2 + 4x0.34 and IE FC RJ-45 modular outlet
Introduction
The individual steps required to assemble an IE hybrid cable 2x2+ 4x0.34 and an IE FC RJ-
45 modular outlet are explained below.
Note the information in the assembly instructions of the plug.
Note
Instructions for assembly
The IE Hybrid Cable 2x2 + 4x0.34 6XV1870--2J is not suitable for operation of the 2FE
insert or 1GE insert!
The insulation-piercing contacts of the IE FC RJ-45 plug 4x2 can be released and
recontacted with the same cable cross section up to 10 times.
Once the ends of cables have made contact, do not make contact with them again but cut
them off.
Note
Conditions for use of the power insert
Use the power insert only under the following conditions:
Extra-low voltages SELV, PELV to IEC 60364-4-41
In USA/CAN with power supplies according to NEC class 2
In USA/CAN, the cabling must meet the requirements of the NEC/CEC
Current load maximum 0.5 A.