SITOP PSU6200 3ph
Equipment Manual, 02.2020, A5E44623402-1-76
35
Technical data
6
Note
Technical data apply for a rated input voltage, rated load and 25 °C ambient temperature if
nothing else is specified.
6.1
Input
6EP3433-7SB00-0AX0
(24 V/5 A)
6EP3434-7SB00-3AX0
(24 V/10 A)
6EP3436-7SB00-3AX0
(24 V/20 A)
Input
•
Remark
3-phase, AC
2-phase operation: is permis-
sible under the following
general conditions: Output
with max. 80 % I
out rated
,
U
in
> 360 V,
T
amb
< 60 °C
3-phase, AC
2-phase operation: is permis-
sible under the following
general conditions: Output
with max. 100 % I
out rated
,
U
in
> 360 V,
T
amb
< 60 °C
3-phase, AC
2-phase operation: is permis-
sible under the following
general conditions: Output
with max. 80 % I
out rated
,
U
in
> 360 V,
T
amb
< 60 °C
Rated voltage U
in rated
AC: 400 - 500 V
Voltage range
•
Remark
AC: 323 - 576 V; DC: 450 V - 600 V
Derating for U
in
< 360 V AC: max. x % I
out rated
:
90
-
-
Wide-range input
Yes
Switch-in/switch-out thresh-
old, typical
286 V AC / 239 V AC
310 V AC / 270 V AC
310 V AC / 270 V AC
Line failure buffering at
I
out rated
, min.
22 ms
25 ms
25 ms
Line failure buffering
at 400 V AC
Rated line frequency
50 - 60 Hz
Line frequency range
47 - 63 Hz
Input current for rated input
voltage 400 V DC
0.4 A
0.4 A
0.9 A
Input current for rated input
voltage 500 V DC
0.3 A
0.3 A
0.7 A
Inrush current limiting
(25 °C), max.
22 A
13 A
17 A
I²t, at 400 V AC, max.
0.15 A
2
s
0.05 A
2
s
0.1 A
2
s
I²t, at 500 V AC, max.
0.25 A
2
s
0.05 A
2
s
0.1 A
2
s
Integrated input fuse
None
None
None
Summary of Contents for 6EP3433-7SB00-0AX0
Page 8: ...Safety instructions SITOP PSU6200 3ph 8 Equipment Manual 02 2020 A5E44623402 1 76 ...
Page 22: ...Mounting removal SITOP PSU6200 3ph 22 Equipment Manual 02 2020 A5E44623402 1 76 ...
Page 54: ...Ambient conditions SITOP PSU6200 3ph 54 Equipment Manual 02 2020 A5E44623402 1 76 ...
Page 62: ...Environment SITOP PSU6200 3ph 62 Equipment Manual 02 2020 A5E44623402 1 76 ...