Siemens IK PI · 2004
6/67
AS-Interface Slaves
I/O modules for operation in the field
Digital I/O modules IP67 - application modules
6
■
Technical specifications
(continued)
2 x (1 input/1 output)
PNP transistor
3RG9 001–0AJ00
Slave type
Standard slaves
Operational voltage in accordance
with AS-Interface specification in V
26.5 to 31.6
Total current input in mA
£
270
Input connection
PNP
Inputs
• Sensor supply via AS-Interface
Short-circuit and overload proof
• Voltage range in V
20 to 30
• Load rating for all inputs in mA
200
• Connection of sensors
2-wire system
• Switching level High in V
³
10
• Input current Low/High in mA
£
1.5 /
³
5
Outputs
• Type of output
Electronics
• Current carrying capacity per
output in A DC 12 / DC 13 typ.
0.2
• Maximum summation current
per module in A
0.2
• External supply voltage
Not required
• Short-circuit protection
Built-in
• Inductive interference protection
(free-wheeling diode)
Built-in
• External 24 V DC supply voltage
The outputs are supplied via the
yellow AS-Interface cable
• Watchdog
Built-in
Connection of AS-Interface
EMI
I/O configuration
3
ID code
F
Assignment of data bits
• Socket 1
Input D0 and output D2
• Socket 2
--
• Socket 3
Input D1 and output D3
• Socket 4
--
AS-Interface certificate
Yes
Approvals
UL, CSA, ship building
Degree of protection
IP67
Ambient temperature in °C
-25 to +85
Storage temperature in °C
-40 to +85
Number of I/O sockets
2
I/O display
Yellow LED
AS-Interface voltage display
Green LED
Diagnostics
Without LED
Connection
Via contact pin on the FK or Pg
coupling module
Note
The black AS-Interface cable is
not required
4-fold distributor passive
without LED
3RG9 001-0AD00
Function
The passive 4V application mod-
ule is used for connecting the
intelligent I/O to the AS-Interface
Operating voltage in V
26.5 to 31.6 DC (AS-Interface)
Voltage range in V
20 to 30 DC
Current load for all total in A
2
Socket assignment
1 = AS-i ”+“3 = AS-i ”–“
Connection
4 x M12 socket for connecting AS-
Interface (Sensors/actuators)
Degree of protection
IP67
Ambient temperature in °C
–25 to +85
Non-operating temperature in °C
–40 to +85
Number of M12 sockets
4
Connection
Via contact pin on the FK or Pg
coupling module