Siemens IK PI · 2004
6/95
AS-Interface Slaves
Special integrated solutions
AS-Interface communication modules
6
■
Overview
(continued)
AS-Interface communication module for circuit-board
mounting 3RK1400-1CD00-0AA2
1) Note: For pad numbering, see the Section
Dimensional Drawings
Via the 4I/4O module for PCB mounting, up to four mechanical
switches or 3-wire sensors to IEC 947-5-2 can be connected or
indicator lamps can be controlled, whereby the short-circuit-
proof electronic switching outputs are supplied from an auxiliary
voltage (24 V PELV).
It is mounted easily via a "Card edge board-to-board-connec-
tor“. This can be ordered, for example, from the company AMP
for vertical and horizontal mounting:
• 180° version for vertical mounting (from AMP):
Order No. 530843-2
• 90° version for horizontal mounting (from AMP):
Order No. 650118-1
If the inputs are loaded with more than 200 mA, the module will
not respond to master calls.
AS-Interface communication module for circuit-board
mounting 3RK1200-0CD00-0AA2
1) Note: For pad numbering, see the Section
Dimensional Drawings
Via the 4I module for PCB mounting, up to four mechanical
switches or 3-wire sensors can be connected, whereby the in-
puts are supplied from the AS-Interface cable.
It is mounted easily via a "Card edge board-to-board connector“.
This can be ordered for example from the company AMP for ver-
tical and horizontal mounting:
• 180° version for vertical mounting (from AMP):
Order No. 530843-2
• 90° version for horizontal mounting (from AMP):
Order No. 650118-1
If the inputs are loaded with more than 200 mA, the module will
not respond to master calls.
Connection
Connection pad
1)
ASi+
27, 29
ASi-
28, 30
17, 18, 23, 24
Sensor-
13, 14, 19, 20
IN1
21
IN2
22
IN3
15
IN4
16
U
Aux
+ (L24+)
2, 4
U
Aux
- (M24)
1, 3
OUT1
9
OUT2
10
OUT3
5
OUT4
6
OUT-
7, 8
Unused
11, 12, 25, 26
Connection
Connection pad
1)
ASi+
27, 29
ASi-
28, 30
17, 18, 23, 24
Sensor-
13, 14, 19, 20
IN1
21
IN2
22
IN3
15
IN4
16
Unused
1, 2, 3, 4, 5, 6, 7, 8, 9,
10, 11, 12, 25, 26