Technical Data
3TK2845 Multifunction Device Manual
3-2
GWA 4NEB 926 2087-22 DS 01
3.1
Technical Data
Type
3TK2845-.....
Specifications
EN 60204-1, EN 954-1, IEC 61508
EMC
EN 60947-5-1
Category according to EN 954-1
4
Safety Integrity Level (SIL)
3
Test certifications
TÜV (German Technical Inspectorate)
Rated insulation voltage U
i
300 V
Rated impulse withstand voltage U
imp
4 kV
Rated supply voltage U
s
24 V DC
Operating range
0.85 to 1.15 U
s
Rated power consumption
2.5 W
Short-circuit protection
Short-circuit-proof, use fuse links at the
isolated protected outputs: LV type 3NA,
DIAZED type 5SB, NEOZED type 5SE
Switching frequency z during rated operation
2000 1/h
Response time
max. 60 ms
Release time, (Stop category 0) during
EMERGENCY-STOP
45 ms
Release time, (Stop category 1) at the safe
outputs during EMERGENCY-STOP
max. 300 seconds (adjustable)
Mains buffering
25 ms
Recovery time during EMERGENCY-STOP/
power failure
min. 200 ms/min. 8 seconds
Min. recommended duration of EMERGENCY-
STOP command
30 ms
Duration of command for START button
0.2 to 5 seconds
Permissible ambient temperature T
a
during
operation and storage
–25 up to +50 °C/–40 up to +80 °C
Total resistance of sensor circuit R
SG
Max. 250
Ω
Total capacity of sensor circuit C
SG
Max. 500 nF
Degree of protection according to EN 60529,
casing/terminals
IP20
Shock-hazard protection, DIN VDE 0106/Part
100
Protection against direct contact
Weight
0.4 kg
Permissible mounting position
Any
Shock resistance
Sine wave 8/10 and 15/5 g/ms
Table 3-1: Technical Data
Summary of Contents for 3TK2845
Page 6: ...3TK2845 Multifunction Device Manual iv GWA 4NEB 926 2087 22 DS 01 ...
Page 38: ...Functional Information 3TK2845 Multifunction Device Manual 2 26 GWA 4NEB 926 2087 22 DS 01 ...
Page 44: ...Technical Data 3TK2845 Multifunction Device Manual 3 6 GWA 4NEB 926 2087 22 DS 01 ...
Page 66: ...3TK2845 Multifunction Device Manual 5 16 GWA 4NEB 926 2087 22 DS 01 ...
Page 68: ...3TK2845 Multifunction Device Manual GWA 4NEB 926 2087 22 DS 01 ...