A.3.5
Measured value - data set (index) 94
Data set (index) 94 - measured values
Note
Bits that are not described in the tables below are reserved and should be ignored.
Note
Sub-indices are not supported.
Table A-4
Data set (index) 94 (measured values) - solid-state overload relay for IO‑Link
Byte.Bit
Description
0.0 ... 0.7
Phase current I (L1
rms
in 3.125% steps)
1.0 ... 1.7
Phase current I (L2
rms
in 3.125% steps)
2.0 ... 2.7
Phase current I (L3
rms
in 3.125% steps)
3.0 ... 27.7
Reserved
28.0 ... 31.7
Phase current I (L1
rms
in 0.01-A steps)
32.0 ... 35.7
Phase current I (L2
rms
in 0.01-A steps)
36.0 ... 39.7
Phase current I (L3
rms
in 0.01-A steps)
Example of relative value in [%] phase current I (L1
rms
), Byte 0:
0x1E = 30 dec. → 30 • 3.125 = 93.75%
Example of absolute value in [A] phase current I (L1
rms
), Byte 28 - 31:
00x00007A34 = 31284 dec. → 31284 • 0.01 A = 312.84 A
Note
In the case of non-acknowledgeable faults (see Chapter "Fault codes (only in the case of non-
acknowledgeable faults) (Page 104)"), the current value registers in data set 94 always show
maximum values:
• Phase current I (L1
rms
in 3.125% steps) = 0xFF
• Phase current I (L2
rms
in 3.125% steps) = 0xFF
• Phase current I (L3
rms
in 3.125% steps) = 0xFF
• Phase current I (L1
rms
in 0.01-A steps) = 0x7FFFFFFF
• Phase current I (L2
rms
in 0.01-A steps) = 0x7FFFFFFF
• Phase current I (L3
rms
in 0.01-A steps) = 0x7FFFFFFF
Appendix
A.3 Data sets
SIRIUS 3RB24 electronic overload relay for IO-Link
Equipment Manual, 07/2022, NEB969165602000/RS-AA/003
123