Note
Sub-indices are not supported.
Table A-6
Data set (index) 131 (technology functions) - solid-state overload relay for IO‑Link
Byte.Bit
Bit length
Access
Description
0 ... 7
64
—
Reserved
8.5
1
r/w
Ground fault detection
2)
0 = Disable; 1 = Enable
9 ... 10
16
—
Reserved
11.3
1
r/w
Cold start
1)
0 = Disable; 1 = Enable
12 ... 15
32
r
Rated operational current
3)
(in 0.01 A steps)
16 ... 17
16
—
Reserved
18.0 ... 18.1
2
r
Response to overload - thermal motor model
4)
0 = Tripping without restart (MAN);
1 = Tripping with restart (AUTO)
18.2 ... 18.7
6
—
Reserved
19.0 ... 19.3
4
r
Trip class [CLASS]
CLASS 5 = 0x03
CLASS 10 = 0x00
CLASS 20 = 0x01
CLASS 30 = 0x02
19.4 ... 19.7
4
—
Reserved
20 ... 23
32
—
Reserved
24.0
2
r
Response to overload - thermistor
5)
0 = Tripping without restart (MAN);
1 = Tripping with restart (AUTO)
24.2 ... 24.6
5
—
Reserved
24.7
1
r
Thermistor - monitoring
0 = No; 1 = Yes
1)
You can find more information on the "Cold start" parameter in Chapter ""Cold start" parameter
(Page 51)".
2)
You can find more information on the "Ground fault detection" parameter in Chapter ""Ground
fault detection" parameter (Page 52)".
3)
You can find more information on the "Rated operational current" parameter in Chapter ""Rated
operational current" parameter (Page 53)".
4)
You can find more information on the "Response to overload - thermal motor model" parameter
in Chapter ""Response to overload - thermal motor model" parameter (Page 55)".
5)
You can find more information on the "Response to overload - thermistor" parameter in Chapter
""Response to overload - thermistor" parameter (Page 56)".
Appendix
A.3 Data sets
SIRIUS 3RB24 electronic overload relay for IO-Link
Equipment Manual, 07/2022, NEB969165602000/RS-AA/003
125