12
3 Description
3.1.8 Anti-Condensation Heaters
Control cubicle
90 W
Operating mechanism
210 W
Table 6 Anti-condensation heaters
The anti-condensation heaters must always be
switched on.
3.1.9 Reference Contact IK-3
Principle
Fixed Hall sensor and moving magnet
Hall sensor
HE-6103
Magnet
HE-6104
Supply voltage
24VDC
Operating tempera-
ture
-40°C ... +85°C
Output
4...20 mA, CLOSE: >18 mA, OPEN: <6 mA
Resolution
<0,2 ms
Transmission
Current loop, max. 500 m
Table 7 Technical Data IK-3
3.1.10 Further Technical Data
)
Note
Technical Data for
- Trip
voltage
- Control
voltage
- Heater
voltage
-
Pressure monitoring for SF
6
-
Charging motor of the spring drive mecha-
nism
are indicated in the circuit diagram.
)
Note
Technical Data for
- Circuit-breaker
weights
-
the permitted cable pull F
are indicated in the dimension drawing.