Document No. 129-104 
Installation Instructions 
October 1, 2013 

 

Page 4 of

 

5

 

Siemens Industry, Inc.

 

 

1
2
3
4
5
6

7
8
9

10
11
12

SEN0485R1

 

CAUTION: 

 

  To prevent equipment damage, do the 

following:  

If room unit is powered by AC (See Figure 
8.): 

 

AC Supply must be type NEC Class 
2 and earth grounded at the 
secondary neutral. 

 

Room Unit ACN (GND) must be 
connected to the controller common. 

 

If the controller has a floating 
common, that common must be 
connected to the same earth ground 
point as the controller AC supply. 

If room unit is powered by isolated DC 
(See Figure 7): 

 

Where power is current limited up to 
300 mA, it is not required to earth 
ground the controller isolated 
common. 

 

Room Unit DC-(GND) must be 
connected to the controller common. 

Figure 6.  Typical Wiring Base. 

(All terminals may not be present.) 

Pin No. 

Function 

QFA3212.EWSN or QFA32SS.EWSN 

 

DC+ or ACH 

 

DC- or ACN (GND) 

 3 

Temp 

Output 

 4 

Humidity 

Output

 

 5* 

Passive 

Temp 

 

6* 

Passive Temp Common 

QFA3212.FWSN or QFA32SS.FWSN 

 

DC+ or ACH 

 

DC- or ACN (GND) 

 3 

Temp 

Output 

 4 

Humidity 

Output

 

 5* 

Passive 

Temp 

 

6* 

Passive Temp Common 

 7 

Setpoint 

Output

 

 8 

Override

 

 9 

Override 

Common

 

 

CAUTION: 

 

  Follow manufacturer’s Installation 

Instructions and Wiring Guidelines for 
connecting the controller to the Room 
Unit. 

  APOGEE Controllers with common 

already earth grounded are TXIO used 
on PXC Modular, PXC Compact 36 
Expansion and P1 BIM or PTM used 
on MBC and RBC. These do not 
require the earth ground wire to be 
connected to the controller as shown in 
Figure 8. 

  APOGEE Controllers with floating 

common are PXC Compact 16/24/36, 
MEC, PXM, LON TEC and PPM. 
These require the earth ground wire to 
be connected to the controller as 
shown in Figure 8. 

* Not available on “SS” models. 

NOTE: 

If active temperature (0-5V/0-10V/4-20 mA)  
(Pin 3) rather than passive/resistive temperature 
is used, Passive Temp Common (Pin 6) does 
not need to be terminated. 

The installation is now complete. 

 

 

Summary of Contents for 2200 Series

Page 1: ...EWSN Accessories AQA2200 INTL Room Unit Back Plate 10 pack AQA2200 2X4 Room Unit Back Plate Single 563 102 GSKT Kit Room Sensor Insulating Gasket 10 pack For hollow wall installations NOTE If installing the Back Plate discard the metric screws provided with the Back Plate and utilize the Room Unit mounting screws Caution Notations CAUTION Equipment damage or loss of data may occur if you do not fo...

Page 2: ...f the device 3 Cut a 1 inch 25 mm center hole with a hole saw NOTE It is recommended that you use the optional Insulating Gasket on the back of the Sensor Base for hollow wall installations When applying the adhesive backed gasket to the back of the Sensor Base orient the gasket so that the cut out arrow portion of the gasket is in the upper lefthand quadrant of the Sensor Base The Sensor Base has...

Page 3: ...e back of the PCA SEN0588R1 F C Figure 5 Changing Display to C 3 Snap the room unit cover to the room unit base plate by first hooking the room unit front to the top latches and then rotating the cover downward until it latches 4 Loosen the safety set screw at the bottom of the base one or two revolutions to lock the cover to the base Be careful not to loosen too far as the screw can be completely...

Page 4: ...or ACH 2 DC or ACN GND 3 Temp Output 4 Humidity Output 5 Passive Temp 6 Passive Temp Common QFA3212 FWSN or QFA32SS FWSN 1 DC or ACH 2 DC or ACN GND 3 Temp Output 4 Humidity Output 5 Passive Temp 6 Passive Temp Common 7 Setpoint Output 8 Override 9 Override Common CAUTION Follow manufacturer s Installation Instructions and Wiring Guidelines for connecting the controller to the Room Unit APOGEE Con...

Page 5: ...ution Figure 8 Externally AC Powered 2200 Room Units NOTE Externally DC powered 2200 Room Units require isolated DC supply with all commons connected and may be used on the same controller with other Room Units powered by Internal Sensor Supply NOTE Externally AC powered 2200 Room Units require controller common and all AC secondary neutral ACN to be earth grounded and may be used on the same cont...

Reviews: