background image

Document No. 129-104 
Installation Instructions 
October 1, 2013 

 

Page 2 of 5

 

Siemens Industry, Inc.

 

Mounting Information 

Always mount the room unit vertically. 
 
Locate the room unit: 

 

according to design specifications and local 
regulations. 

 

where the air circulates around it freely (not in 
recessed areas or behind doors). 

 

allowing a minimum of 4 inches (10 cm) free 
space above and below for proper airflow, the 
front cover removal tool, and the computer 
communication cable. 

 

away from drafts caused by doors, windows, 
outside walls, air registers, pipes, return air 
plenums, etc. 

 

away from heat sources such as strong lights, 
fireplaces, direct sunlight, etc. 

 

on an inside wall (preferably), about 5 feet 
(1.5 m) above the finished floor. 

Drywall Mounting (No Rough-in), 
Typical 

Base Plate Mounting and Wiring 

1.  Mark the center (cable) hole and the mounting hole 

locations, using the room unit base plate as a 
template. See Figure 3. 

2.  Drill two 3/16-inch (4.8 mm) mounting holes and 

mount the two plastic wall anchors flush to below the 
wall surface for stable mounting of the device. 

3.  Cut a 1-inch (25 mm) center hole with a hole saw.  

NOTE: 

It is recommended that you use the 
optional Insulating Gasket on the back of 
the Sensor Base for hollow wall 
installations. 
 
When applying the adhesive-backed 
gasket to the back of the Sensor Base, 
orient the gasket so that the cut-out 
arrow portion of the gasket is in the 
upper lefthand quadrant of the Sensor 
Base. The Sensor Base has an UP arrow 
molded into the surface in the same 
quadrant location (see Figure 6). 

 

Figure 2.  Insulating Gasket. 

4.  Pull about three inches (75 mm) of the cable through 

the hole in the base plate. 

5.  Mount the room unit base plate on the wall, noting 

the UP arrow: 

NOTE: 

If required, position the Back Plate 
behind the Room Unit Base, aligning the 
top and bottom mounting holes, prior to 
mounting to the wall: 

a.  Install the two mounting screws provided, but 

do not tighten. 

b.  Level the room unit base plate for appearance. 

c.  Tighten the two mounting screws to the room 

unit base plate. 

6.  Cut the cable, leaving about three inches (75 mm) 

on the room unit side of the drywall. Ensure that pin 
Number 1 connects to the same wire at each end of 
the cable.  

 

NOTE: 

See Figure 2 for details on optional Gasket 
application. 

Figure 3.  Drywall Mounting (No Rough-in), Typical. 

Summary of Contents for 2200 Series

Page 1: ...EWSN Accessories AQA2200 INTL Room Unit Back Plate 10 pack AQA2200 2X4 Room Unit Back Plate Single 563 102 GSKT Kit Room Sensor Insulating Gasket 10 pack For hollow wall installations NOTE If installing the Back Plate discard the metric screws provided with the Back Plate and utilize the Room Unit mounting screws Caution Notations CAUTION Equipment damage or loss of data may occur if you do not fo...

Page 2: ...f the device 3 Cut a 1 inch 25 mm center hole with a hole saw NOTE It is recommended that you use the optional Insulating Gasket on the back of the Sensor Base for hollow wall installations When applying the adhesive backed gasket to the back of the Sensor Base orient the gasket so that the cut out arrow portion of the gasket is in the upper lefthand quadrant of the Sensor Base The Sensor Base has...

Page 3: ...e back of the PCA SEN0588R1 F C Figure 5 Changing Display to C 3 Snap the room unit cover to the room unit base plate by first hooking the room unit front to the top latches and then rotating the cover downward until it latches 4 Loosen the safety set screw at the bottom of the base one or two revolutions to lock the cover to the base Be careful not to loosen too far as the screw can be completely...

Page 4: ...or ACH 2 DC or ACN GND 3 Temp Output 4 Humidity Output 5 Passive Temp 6 Passive Temp Common QFA3212 FWSN or QFA32SS FWSN 1 DC or ACH 2 DC or ACN GND 3 Temp Output 4 Humidity Output 5 Passive Temp 6 Passive Temp Common 7 Setpoint Output 8 Override 9 Override Common CAUTION Follow manufacturer s Installation Instructions and Wiring Guidelines for connecting the controller to the Room Unit APOGEE Con...

Page 5: ...ution Figure 8 Externally AC Powered 2200 Room Units NOTE Externally DC powered 2200 Room Units require isolated DC supply with all commons connected and may be used on the same controller with other Room Units powered by Internal Sensor Supply NOTE Externally AC powered 2200 Room Units require controller common and all AC secondary neutral ACN to be earth grounded and may be used on the same cont...

Reviews: